Last week, job nearly done, the bird's due back on the line...and then the firefighting system goes off. Allegedly for the third time in three weeks. To cut a long story short, fleet 6452 has now been patched up ready to limp off to the heavy maintenance guys at Timco to try to turn back into something rather more presentable.
Extraordinary pictures, and the worksheet for the job - which as you'll see became a little extended - below.
Here's the version of events passed to me:
Bay 9 and 12 ORD.
B767's. 1,000 psi water canons take out 11 windows of a 767 - 6452.
A foreman runs up & pulls down the window shades as they shatter in his face.
Mechanics stand around and smile.
A failing company pays the lowest bidder to install a new deluge system that goes off
three times in three weeks unnecessarily.
West bay. East bay. Now...the far east bay.
Even the fire department quit stopping by as it goes off again.
They pay fire control contractors more than they pay us, but at least we gave them a quality product.
Now...they get what they pay for.
The 767's? Probably ferry them back to TIMCO for rehab. Don't even want to know the total cost of repairs, replacing all cockpit CRT's etc must be big $$. No doubt this plane will be giving us trouble down the road.
»AMSDIS / 6452 / ALL/ / F / 3782220 ACFT DATA DISPLAY
BP8015 :PRI-4 RPL BORROWED PART
REF PTT SEQ 3782163 PTT 72378 PTC 11783 DDMMMYY ORD RPL
BORROWED PART INDICATED BELOW, RMV BOROWED PART PAPER WORK (IF
ANY) FROM AC MTC BOOK. COMPLETE & ATTACH RED-STRIPE PART RMVL
TAG & ROUTE THRU STORES FOR RTN TO LENDOR. :REPLACED FO'S STAB
TRIM INDICATOR OPS CHKS GOOD.INSTALLED AMERICAN AIRLINES
PART.PN40-6 18-11 SN 012.CONTAINER PLACED IN LOB.**PAC ORDER
PLACED FOR 481-0483 OSTF# F5458 SFOLM GUZMAN**
CAT: TR: 4D MR:N MTR: CAL:Y POS: ATA:27 -
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782219 ACFT DATA DISPLAY
3782220 17FEB ORD ACP :THE ACFT HAS HAD A VISUAL INSP BY A
CERTIFIED MECHANIC OR REPAIRMAN AND THE CONTROLLER HAS
DETERMINED THAT THE ACFT IS IN A COND FOR SAFE FLIGHT FOR A TYPE
II FERRY FROM ORD TO GSO FOR REPAIR BY GSOMM WITH: INTERNAL
PASSENGER COMPARTMENT SIDEWALL PANELS ON RIGHT SIDE BUSINESS
CLASS REMOVED AND STOWED IN AFT BULK CARGO PIT. PASSENGER CABIN
WINDOW AT #1 RT AND RH OVERWING EXIT DOOR EXT INSP ACP BUT WILL
REQUIRE INTERNAL INSPECTION AND POSSIBLE RPL IN GSO.
:ACCOMPLISHED VISUAL INSP
PARTS: NONE NEEDED
INSP: MR:N POS: ATA: 000-
»AMSDIS / 6452 / ALL/ / F / 3782218 ACFT DATA DISPLAY
CF0769 17FEB ORD CF -T :PRI-1U A-C REQUIRED A CAT III DUE TO
MCP RPL'D. UNABLE TO ACCOMPLISH DUE TO CENTER A-P NOT ENGAGING.
SEE DF768. A-C DOWN GRADED TO CAT I UNTIL CAT III TEST CAN BE
ACCOMPLISHED. BY- 42489 :.
PLACARD: 9999 -
**DEFECT IDENTIFICATION** AIRCRAFT REMOVED FROM CAT II STATUS
PARTS: NONE NEEDED
AUTH: ORDMM WIATER DE CF REF: MM22-10-99 PG201
CAT:U TR: 20D MR:N MTR:AC CAL:Y POS: ATA:22 -
»AMSDIS / 6452 / ALL/ / F / 3782217 ACFT DATA DISPLAY
DF0768 17FEB ORD DF -T :PRI-1C NEED TO ACCOMPLISH AUTOPILOT AND
AUTOTHROT TLE CAT III OPERATIONAL TEST REFMM22-10-00 BY- 94914
:CENTER A-P WILL NOT ENGAGE. CURRENT FAULTS- NO INFC FCC C MCP
A-P ENG DISC AND NO INFC FCC C MCP A-P ARM IN. REPLACED MCP NO
HELP. SWAPPED FCC'S NO HELP.
PLACARD: 2210C -
DEFECT:
CENTER AUTOPILOT INOPERATIVE.
COCKPIT BREAKER(S) PULLED AND SAFETIED:
ONE OF THE FOLLOWING MAY BE PULLED:
(E17) FLT CONT CMPTR PWR L
(E20) FLT CONT CMPTR PWR C
(E35) FLT CONT CMPTR PWR R
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782215 ACFT DATA DISPLAY
3782217 17FEB ORD RPL :3RD DIGIT IN IAS-MACH WINDOW STICKS.
BY- 42489 :REPLACED MCP PER MM 22-11-02.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:22 -
3782216 17FEB ORD ACP :NEED TO PRESSURIZE AIRCRAFT TO CHECK
FOR A IR LEAKS AFTER WINDOW INSTALLATION. BY- 48312 :ACCOMPLISH
SUCCESSFUL CABI N LEAKAGE TEST REV MM05-51-24.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:21 -
»AMSDIS / 6452 / ALL/ / F / 3782213 ACFT DATA DISPLAY
3782215+17FEB ORD ACP :LAVATORY WASTE LEVEL SERVICE CHECK
:WASTE LEVEL ZERO, WATER LE VEL FULL
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:050000-01
3782214 17FEB ORD CON :ALL RT. SIDE BUSINESS CLASS SIDEWALLS
HAVE BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL
SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN
THE AFT BULK CARGO PI T. CONT OF AMIS ITEM 3782198 :WINDOW
REVEALS AND SHADES ALSO REMOVED FROM FIRST 7 PAX WINDOWS ON RH
SIDE
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782212 ACFT DATA DISPLAY
3782213 17FEB ORD ACP- :EG1956 REPLACE WINDOW ASSYS
DUE TO EXPOSURE TO HIGH PRESSURE FIRE SUPRESSION CANNON REPLACE
ALL RIGHT SIDE AIRCRAFT WINDOW ASSYS OR PLUGS, ALL SPRING ATTACH
CLIPS AND ATTACH HARDWARE FROM STA 368 THRU STA 883.5. ADDITION
ALLY REPLACE ANY DAMAGED (BENT, CRACKED, WARPED, OR PULLED) NUT
PLATE, RIVET, OR SPRING CLIP ATTACH BRACKET OR STANCION ON ALL
AFFECTED WINDOWS. RECORD ALL DEFECTS AND CONTACT ENGINEERING BEF
ORE FURTHER FLIGHT. ORDLE MICHAEL YOURG
:REPLACED RT SIDE WINDOWS, ATTACH HARDWARE AND CLIPS REF PTT
SEQUECNCE #'S 3782185, 3782184 , 3782172, 3782171, 3782192. WILL
ACCOMPLISH #1R AND OW EXITS SE PERATELY.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782211 ACFT DATA DISPLAY
DF0767 17FEB ORD DF -T :PRI-4U DUE TO WATER ENTERING INTO CABIN
AREA IN FIRST AND BUISNESS CLASS INOP THE IFE SYSTEM. BY- 99438
:IFE SYSTEM INOP.NEEDS SYST EM CHECK OF EACH SEAT.CB PULLED AND
COLLARED P36 D3
PLACARD: 2520HY -
DEFECT:
INFLIGHT ENTERTAINMENT SYSTEM INOPERATIVE.
FLIGHT CREW:
A. FLIGHT ATTENDANTS MUST PREFORM LIVE SAFETY DEMONSTRATION.
B. ADVISE PURSER.
ONBOARD SERVICES:
A. PREFORM LIVE SAFETY DEMONSTRATION.
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782211 ACFT DATA DISPLAY
CUSTOMER SERVICE:
A. CONSIDER INOPERATIVE VIDEO EQUIPMENT UNITS WHEN ASSIGNING
PASSENGERS TO FLIGHT
PARTS: NOT RECORDED
AUTH: ORDMM TALDONE J MEL REF: 2520HY
CAT:U TR:CK MR:N MTR:CIP CAL:Y POS: ATA:251 -
ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD
»AMSDIS / 6452 / ALL/ / F / 3782210 ACFT DATA DISPLAY
3782211 17FEB ORD OK :RESET C.B'S PULLED FOR HI RANGE LEAK
CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER
C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST
COMPLETE. CONT OF AMIS ITEM 3782182 :ELEVATOR FEEL TEST
ACCOMPLISHED. STARTED TO RESET CIRCUIT BREAKERS. M. ARMENTA
027552 CONT OF AMIS ITEM 3782197 :RESET C-B'S PER MM
34-11-00-503.FOUND LEFT AND RIGHT STICK SHAKER C-B'S ALREADY RES
ET.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
»AMSDIS / 6452 / ALL/ / F / 3782208 ACFT DATA DISPLAY
3782210 17FEB ORD OK :RETURN PITOT STATIC EQUIPMENT AFTER
ELEVAT OR FEEL TEST COMPLETE. BY- 05013 :RETURNED PITOT STATIC
EQUI PMENT TO TOOL ROOM.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782209 17FEB ORD OK :ELEVATOR FEEL STATIC VISCO JET DRAINS
TAPE D AND SEALED FOR PITOT STATIC TEST IN STAB COMPARTMENT,ALSO
BLAN KETS INSTALLED,REMOVE AFTER COMPUTER REPLACEMENT. BY- 05013
:REMOVED TAPE AND CAPS FROM ELEVATOR FEEL STATIC VISCO JET
DRAINS ALSO REMOVED BLANKETS AND RAGS FOUND IN STAB COMPARTMENT.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782207 ACFT DATA DISPLAY
3782208 17FEB ORD SEC :NEED TO REMOVED BUSINESS CLASS RIGHT
SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-
103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET. CONT OF AMIS
ITEM 3782013 :CLOSET REINSTALLED. NEED T O INSTALL COVER PLATE
IN LOWER FWD CUBBY HOLE. CONT OF AMIS ITEM 3782190 :SECURED
COVER PLATE IN RIG HT HAND SIDE CLOSET AND RESECURED O2 BOTTLES
IN CLOSET.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782205 ACFT DATA DISPLAY
3782207 17FEB ORD OK :REMOVE PLASTIC CAPS AND ORANGE TAPE
FROM ELEVATOR FEEL STATIC LINES, IN STAB COMPARTMENT BELOW AND
AFT OF PRESSURE BULKHEAD. BY- 42489 :REMOVED PLASTIC CAPS AND T
APE FROM ELEVATOR FEEL STATIC VISCO JET DRAINS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782206 17FEB ORD OK :PLEASE RETURN 2 EXTENTION CORDS
(K11H01), 1 ENTENTION CORD ON REEL (K05AN05) AND 4 ADAPTERS
(K09A039), THE Y ARE USED FOR FANS TO DRY THE INTERIOR OF CABIN.
BY- 92662 :RETURNED REEL KIT K05AN05 ONLY. CONT OF AMIS ITEM
3782175 :RETURNED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:05 -
»AMSDIS / 6452 / ALL/ / F / 3782203 ACFT DATA DISPLAY
3782205 17FEB ORD OK :3 EA CABIN DOOR SAFETY BARRIERS
INSTALLED NEED TO BE RETURNED TO TOOL ROOM WHEN WORK COMPLETE.
BY- 68654 :RETURNED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:52 -
3782204 17FEB ORD OK :NEED TO ACCOMPLISH OPERATION TEST OF
MAIN (LEFT ,RIGHT,CENTER) HYDRAULIC SYSTEM REFMM29-11-00 BY-
94914 :ACP TO 29-11-00 UP TO 2D N EED TO RUN ENGINES FOR
REMAINDER OF CK CONT OF AMIS ITEM 3782145 :SYSTEM OPS CHKS GOOD
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:29 -
»AMSDIS / 6452 / ALL/ / F / 3782201 ACFT DATA DISPLAY
3782203 17FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF
WING THERMAL ANTI-ICE(30-11-00)ENGINE INLET THERMAL
ANTI-ICE(30-21-0 0) BY- 94914 :SYSTEM OPS CHKS GOOD
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
3782202 17FEB ORD OK :NEED TO ACCOMPLISH AC POWER OPERATIONAL
CH ECKREFMM24-22-00 BY- 94914 :SYSTEM OPS CHKS GOOD
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
»AMSDIS / 6452 / ALL/ / F / 3782200 ACFT DATA DISPLAY
3782201 17FEB ORD ACP :RH MID LAV NEEDS TO BE REMOVED FOR
ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.
CONT OF AMIS ITEM 3782038 MAINT TEXT: CONFIG 2. :REINSTALLED
LAV, NEED TO INSTALL TOILET AND WATER LINES CONT OF AMIS ITEM
3782191 :FINISHED INSTALLATION
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:250 -
»AMSDIS / 6452 / ALL/ / F / 3782199 ACFT DATA DISPLAY
DF0766 17FEB ORD DF -T :PRI-4U ARMREST INNER SHROUD DAMAGED AT
6C BY- 02378 :NEEDS ARM COVER 021-4353 CONT OF AMIS ITEM 3782168
PLACARD: 2520MR -
DEFECT:
PASSENGER ARMREST TRAY TABLE(S) INOPERATIVE.
FLIGHT CREW:
A. ARMREST TRAY TABLE(S) RESTRICTED FROM USE AND SECURED IN
STOWED POSITION OR REMOVED.
B. ADVISE PURSER.
ONBOARD SERVICES:
A. ARMREST TRAY TABLE(S) RESTRICTED FROM USE AND SECURED IN
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782197 ACFT DATA DISPLAY
3782199 17FEB ORD ACP :INSTALL # 2 WINDOW REVEAL REF MM
56-21-01. BY- 39374 :ALL WINDOW REVEALS AND SID EWALL PANELS ARE
IN THE BULK LOADING CARGO PIT,AIRCRAFT IS TO BE FERRIED TO GSO
FOR INTERIOR REPAIR.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
3782198 17FEB ORD CON :ALL RT. SIDE BUSINESS CLASS SIDEWALLS
HAVE BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL
SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN
THE AFT BULK CARGO PI T.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782196 ACFT DATA DISPLAY
3782197 17FEB ORD CON :RESET C.B'S PULLED FOR HI RANGE LEAK
CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER
C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST
COMPLETE. CONT OF AMIS ITEM 3782182 :ELEVATOR FEEL TEST
ACCOMPLISHED. STARTED TO RESET CIRCUIT BREAKERS. M. ARMENTA
027552
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
»AMSDIS / 6452 / ALL/ / F / 3782194 ACFT DATA DISPLAY
3782196 17FEB ORD ACP :IN REF TO SMC 185 IPC REF 32-12-01-020
PAGE 4 ITEM #439 (IPC SHOW ITEM #436 WHICH IS FOR LEFT GEAR DOOR
). OLD PARTS ATTACHED TO RH MLG GEAR DOOR. BY- 97617 :INSTALLED
NEW ANGLE AND HA RDWARE.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:32 -
3782195 17FEB ORD RPL :ELEVATOR FEEL COMPUTER HAS STATIC #2
INTER NAL LEAK. BY- 05013 :REPLACED ELEVATOR FEEL COMPUTER &
ACCOMPLISHED OPS CHECK PER MM27-31-19 AND MM27-31-00. ALL OPS
CHECKS GOOD.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782192 ACFT DATA DISPLAY
3782194 17FEB ORD RPL :RH MLG DOOT TO WING FAIRING SEAL ASSY
ROB FOR ACFT 6459 OSTF S0832 U3252 BY- 94032 :REPLACED WING TO
FAIRING S EAL ASSY.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:32 -
3782193 17FEB ORD RPR :MID-LAV TOILET ASSY HAS A BROKEN LUG ON
GROUNDING WIRE WHERE IT ATTACHES TO BOWL ASSY. BY- 2613
:REPLACED LUG. M. ARMENTA 027552
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:38 -
»AMSDIS / 6452 / ALL/ / F / 3782191 ACFT DATA DISPLAY
3782192 17FEB ORD RPR :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5
EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM
3782170 :RIVETED IN NUT PLATES, INS TALLED NEW WINDOWS
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782189 ACFT DATA DISPLAY
3782191 17FEB ORD CON :RH MID LAV NEEDS TO BE REMOVED FOR
ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.
CONT OF AMIS ITEM 3782038 MAINT TEXT: CONFIG 2. :REINSTALLED
LAV, NEED TO INSTALL TOILET AND WATER LINES
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:250 -
3782190 17FEB ORD CON :NEED TO REMOVED BUSINESS CLASS RIGHT
SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-
103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET. CONT OF AMIS
ITEM 3782013 :CLOSET REINSTALLED. NEED T O INSTALL COVER PLATE
IN LOWER FWD CUBBY HOLE.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782187 ACFT DATA DISPLAY
3782189+17FEB ORD ACP :ACCOMPLISH NON-RII INSPECTION OF BY-
116614MM COMMENTS: ELEVATOR FEEL COMPUTER REPLACEMENT.
:INSPECTED ELEVATOR FEEL CO MPUTER INSTALLATION AND OPERATIONAL
CHECK PER MM27-31-17 401 AND MM27-31-00 PG567. ALL CHECKS GOOD.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:050000-01
3782188 16FEB ORD RPL :4 EACH WINDOW RETAINING CLIP BRACKETS
NEED SOLID RIVETS INSTALLED FOR RT CABIN WINDOW AT STATION 775.
BY- 2613 :AREA WITH SOLID RIVETS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782185 ACFT DATA DISPLAY
3782187 16FEB ORD RPL :2 EACH WINDOW RETAINING CLIP BRACKETS
NEED SOLID RIVETS INSTALLED FOR RT CABIN WINDOW AT STATION 733.
BY- 2613 :AREA WITH SOLID RIVETS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
3782186 16FEB ORD RPL :FLT DECK SEAT COVERS NEED TO BE
REPLACED D UE TO EXCESSIVE WATER
CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT
BACK COV ER. CONT OF AMIS ITEM 3782147 :RPLD CAPTS COVERS.STILL
NE EDS OBSERVER COVERS AOG Z4820 W5004 CONT OF AMIS ITEM 3782167
:REPLACED OBSERVER COVERS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782184 ACFT DATA DISPLAY
3782185 16FEB ORD RPL :THE PLUG WINDOWS ON RIGHT SIDE ADJACENT
TO THE CLOSET AND LAV WILL REQUIRE A MID PANE INSTALLED PRIOR TO
I NSTALLATION ALL EXISTING MID PANES ARE UNSERVICEABLE.NEW PANES
(192-1539)ARE ON AOG J3690. BY- 55690 :REF AMM 56-21-01-0401.
REINSTALLED NEW PLUG AND NEW MID PANE AT STA 787 POSITION ONLY.
CONT OF AMIS ITEM 3782174 :PLUGS INSTALLED ON RIGHT S IDE
STATION 819 & 841 ON SEQ#3782184.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782182 ACFT DATA DISPLAY
3782184 16FEB ORD RPL :REF EG1956 RPL WINDOW ASSEMBLY'S BY-
8087 :RPL WINDOW ASSEMBLY'S AND HARDWARE AT STATION'S
445,489,511,533,555,577,599,621,643,654+33
654+55,654+77,654+99,654+132,687,819 AND 841 REF AMM56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
3782183 15FEB ORD RPL :AIRPHONE CTU UNIT HAS FIRE WATER DAMAGE
BY- 94914 :RPL AIRPHONE CTU REF MM 23 -19-97.CKS OK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782180 ACFT DATA DISPLAY
3782182 15FEB ORD CON :RESET C.B'S PULLED FOR HI RANGE LEAK
CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER
C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST
COMPLETE.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
3782181 15FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHK OF AIR
DA TA SYSTEM REFMM 34-13-00 BY- 94914 :OP CKS OK REF MM.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782179 ACFT DATA DISPLAY
3782180 15FEB ORD ADJ :REF EG1971, NEED TO ACCOMPLISH HI RANGE
LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO
PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489
:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.
ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2
LEAKING. ALL OTHER SYSTEMS OK. CONT OF AMIS ITEM 3782169 :THE
PREV TEXT SHOULD READ CAPT'S S2 AND R AUX S2 HAS A LEAK. CONT OF
AMIS ITEM 3782173 :FOUND ELEVATOE FEEL COMPUT ER INTERNAL
LEAK,SEE SMC 180.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782178 ACFT DATA DISPLAY
3782179 15FEB ORD ACP- :EG1971 INSPECTION PITOT STATIC
CHECK PITOT STATIC SYSTEM TO ENSURE IT IS CLEAR AND FREE OF
FOAM AND OR WATER BY PERFORMING THE FOLLOWING: ACCOMPLISH DRAIN
OF THE PITOT STATIC SYSTEM PER MM TASK 34.11.00.683.001. PERFORM
A FLUSH OF THE ALTERNATE STATIC SYSTEM PER MM TASK 34.11.00.173.
004 NOTING THAT NEITHER THE LH OR RH AIR DATA COMPUTERS NOR THE
ELEVATOR FEEL COMPUTERS PITOT STATIC LINES NEED TO BE DISCONNECT
ED TO PERFORM MM TASK 34.11.00.173.004 (ITEM 3.E.11.) FOR THE
ALTERNATE STATIC SYSTEM ONLY. ACCOMPLISH TASK 34.11.00.735.001
PITOT STATIC SYSTEM TEST. ORDLE MICHAEL YOURG
:ACP REF MM,OP CK NORMAL,NO MOISTURE NOTED,MADE ITEM FOR
ELEVATOR FEEL STATIC 2 LEAK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782176 ACFT DATA DISPLAY
3782178 15FEB ORD RPL :F-O DOME LIGHT LENS COVER IS CRACKED
DUE T O WATER PRESSURE CONTAMINATION BY- 94914 :REMOVED LIGHT
ASSY.AOG N2901 CONT OF AMIS ITEM 3782160 :INSTALLED NEW LIGHT
ASSY
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:33 -
3782177 15FEB ORD RPL :FWD CARGO PIT LOAD STOP BENT IPC
25-53-13 -012 ITEM 205 PART #161-0863 ON AOG C4791 BY- 49297
:PART WRONG ORDERED 120-408 6 PRT ON AOG R3222 CONT OF AMIS ITEM
3782129 :REPLACED PARTIAL LOAD STOP REF MM 25-53-12-401.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:253 -
»AMSDIS / 6452 / ALL/ / F / 3782174 ACFT DATA DISPLAY
3782176 15FEB ORD ACP :2 EA DROP LIGHTS AND 2 EA EXTENSION
CORDS NEED TO BE RETURNED TO TOOL ROOM. BY- 68654 :RETURNED 2 EA
DROP LTS AND EXTENSION CORDS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
3782175 15FEB ORD CON :PLEASE RETURN 2 EXTENTION CORDS
(K11H01), 1 ENTENTION CORD ON REEL (K05AN05) AND 4 ADAPTERS
(K09A039), THE Y ARE USED FOR FANS TO DRY THE INTERIOR OF CABIN.
BY- 92662 :RETURNED REEL KIT K05AN05 ONLY.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:05 -
»AMSDIS / 6452 / ALL/ / F / 3782173 ACFT DATA DISPLAY
3782174 15FEB ORD CON :THE PLUG WINDOWS ON RIGHT SIDE ADJACENT
TO THE CLOSET AND LAV WILL REQUIRE A MID PANE INSTALLED PRIOR TO
I NSTALLATION ALL EXISTING MID PANES ARE UNSERVICEABLE.NEW PANES
(192-1539)ARE ON AOG J3690. BY- 55690 :REF AMM 56-21-01-0401.
REINSTALLED NEW PLUG AND NEW MID PANE AT STA 787 POSITION ONLY.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782172 ACFT DATA DISPLAY
3782173 15FEB ORD CON :REF EG1971, NEED TO ACCOMPLISH HI RANGE
LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO
PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489
:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.
ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2
LEAKING. ALL OTHER SYSTEMS OK. CONT OF AMIS ITEM 3782169 :THE
PREV TEXT SHOULD READ CAPT'S S2 AND R AUX S2 HAS A LEAK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782170 ACFT DATA DISPLAY
3782172 15FEB ORD RPL :RH PASSENGER WINDOW DAMAGED AT STATION
467 . BY- 101373 :INSTALLED NEW RH PASSENGER WINDOW AND HARDWARE
AT STATION 467 PER MM 56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
3782171 15FEB ORD RPL :RH PASSENGER WINDOW DAMAGED AT STATION
423 . BY- 101373 :INSTALLED NEW RH PASSENGER WINDOW AND HARDWARE
AT STATION 423 PER MM 56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782169 ACFT DATA DISPLAY
3782170 15FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5
EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM
3782111 :MANF NEW NUT PLATES AS REQ ED.INSTLED NUT PLATES
BETWEEN FRAME 733 TO 797 AS REQED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782167 ACFT DATA DISPLAY
3782169 15FEB ORD CON :REF EG1971, NEED TO ACCOMPLISH HI RANGE
LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO
PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489
:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.
ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2
LEAKING. ALL OTHER SYSTEMS OK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782168 15FEB ORD CON :ARMREST INNER SHROUD DAMAGED AT 6C BY-
02378 :NEEDS ARM COVER 021-4353
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782165 ACFT DATA DISPLAY
3782167 15FEB ORD CON :FLT DECK SEAT COVERS NEED TO BE
REPLACED D UE TO EXCESSIVE WATER
CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT
BACK COV ER. CONT OF AMIS ITEM 3782147 :RPLD CAPTS COVERS.STILL
NE EDS OBSERVER COVERS AOG Z4820 W5004
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
CF0765 15FEB ORD CF -T :PRI-5U SEAT SHROUD AT 7H DAMAGED BY-
02378 :SHROUD OF SEAT IS PUNCTURE D NEEDS FIBERGLASS
REPAIR.PERFORMED TEMP REPAIR.
PARTS: NONE NEEDED
AUTH: ORDMM TALDONE J CF REF: MOP 05-100-01
CAT:U TR:CK MR:N MTR: CAL:Y POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782163 ACFT DATA DISPLAY
3782165 15FEB ORD OK :SIDEWALL PANELS AT SEATS 6KJ TO 10KJ
ARE TORN,CRACKED,BENT DUE TO HANGER WATER PRESSURE BLOWN THRU
WINDOW S BY- 94914 :PANELS REMOVED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782164 15FEB ORD OK :DUE TO HANGAR FIRE EXTINQISHER WATER
SPRAY SEVERAL CABIN WINDOWS FROM SEATS 6KJ TO 10KJ WERE BLOWN
OUT BY- 94914 :WINDOW REPLACEMENT AND REPAIR COVERED UNDER
EG1956
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782161 ACFT DATA DISPLAY
3782163 15FEB ORD RPL :STAB TRIM INDICATORS HAVE EXCESSIVE
WATER DAMAGE DUE TO HANGER WATER APRAY BY- 94914 :REPLACED
CAPT'S STAB TRIM INDICATOR REF AMM27-48-06, OPS TESTED OK. F-O'S
INDICATOR NEEDS TO BE REPLACED. CONT OF AMIS ITEM 3782157
:REPLACED FO'S STAB TRIM INDICATOR OPS CHKS GOOD.INSTALLED
AMERICAN AIRLINES PART.PN40-6 18-11 SN 012.CONTAINER PLACED IN
LOB.
PARTS: NONE NEEDED
INSP: MR:B POS: ATA:27 -
3782162 15FEB ORD SVC :DRAIN AND FILL POTABLE WATER BY END OF
02- 14 BY- 070484 :DRAINED AND FILLED WATER
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:38 -
»AMSDIS / 6452 / ALL/ / F / 3782159 ACFT DATA DISPLAY
3782161 15FEB ORD SVC :DRAIN AND FILL POTABLE WATER. BY- 70293
:SERVICED WATER 2-15-09
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:38 -
3782160 15FEB ORD CON :F-O DOME LIGHT LENS COVER IS CRACKED
DUE T O WATER PRESSURE CONTAMINATION BY- 94914 :REMOVED LIGHT
ASSY.AOG N2901
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:33 -
»AMSDIS / 6452 / ALL/ / F / 3782157 ACFT DATA DISPLAY
3782159 15FEB ORD ACP :SERVICE H2O ON 02-14-09. BY- 8087
:ACCOMPLISHED THE EMPTYING AND FILLING H2O ON 2-14-09.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:38 -
3782158 14FEB ORD ACP :ALL
COMPONENTS,LIGHTS,SWITCHES,INDICATORS ON PANELS
P1-1,P1-2,P1-3,P2,P3-1,P3-2,P3-3 NEED TO OPS CHECKED WHEN
POWERED UP. BY- 139723 :OPS TESTED NORMAL. AIR DAT A INSTRUMENTS
OPS TO BE ACCOMPLISHED ON SMC 97.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782155 ACFT DATA DISPLAY
3782157 14FEB ORD CON :STAB TRIM INDICATORS HAVE EXCESSIVE
WATER DAMAGE DUE TO HANGER WATER APRAY BY- 94914 :REPLACED
CAPT'S STAB TRIM INDICATOR REF AMM27-48-06, OPS TESTED OK. F-O'S
INDICATOR NEEDS TO BE REPLACED.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:27 -
3782156 14FEB ORD ACP :1ST OBS AND 2ND OBS AUDIO SEL PANELS
REPLA CED,MR NUMBERS RECORDED,NEEDS OP CK. BY- 05013 :TESTED
NORM REF THE AMM23- 51-01
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782153 ACFT DATA DISPLAY
3782155 14FEB ORD ACP :WX RADAR T-R HAS FIRE SPRINKLER WATER
DAMA GE BY- 94914 :REPLACED WX RADAR T-R. REF MM 34-43-01-401.
PLUG AND RACK SHOW NO EVIDENCE OF FURTHER WATER DAMAGE AT THIS
TIME.THE WEATHER RADAR OPERATIONAL TEST, REF AMM 34-43-00-501
WILL NEED TO BE ACCOMPLISHED. CONT OF AMIS ITEM 3782059 :TESTED
NORM REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782154 14FEB ORD ACP :NEED TO INSPECT P87 MISC ELECTRIC EQUIP
PN L FOR WATER CONTAMINATION IN E&E BY- 94914 :INSPECTED PANEL,
NO MOISTU RE NOTED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
»AMSDIS / 6452 / ALL/ / F / 3782151 ACFT DATA DISPLAY
3782153 14FEB ORD ACP :REF EG 1964. CONNECTOR FOR EMERGENCY
EVACUATION SIGNAL PANEL ON FWD CABIN ATTENDANTS' PANEL, FWD OF
1L DOOR, WAS REMOVED AND RECONNECTED. REF MM 25-63-01-P205,
PASSENGER COMPARTMENT EMERGENCY EVACUATION SIGNAL PANEL NEEDS AN
OPERATIONAL TEST. BY- 68654 :TESTED NORM REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:251 -
3782152 14FEB ORD ACP :RADIO ALTIMETER ANTENNA TEST, REF AMM
34-33 -02-406 (E) NEEDS TO BE ACCOMPLISHED DUE TO ANTENNAS
REMOVAL AND REINSTALLATION. BY- 68654 :TESTED NORM REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782149 ACFT DATA DISPLAY
3782151 14FEB ORD ACP :NEED TO COMPLETE OPERATIONAL CHK OF PA
,CA BIN INTERPHONE,FLIGHT INTERPHONE FROM FLT DECK HANDSET REFMM
23- 31-00,23-42-00,23-51-00 BY- 94914 :TESTED NORM REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782150 14FEB ORD ACP :CAPT'S AND F-O EADI'S AND EHSI'S NEED
OP C K DUE TO REPLACEMENT,REF MM34-22-00 BY- 05013 :TESTED NORM
REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782147 ACFT DATA DISPLAY
3782149 14FEB ORD ACP :EFIS NEEDS OP CK DUE TO REPLACEMENT OF
BOT H CTL PNLS AND ALL CRT'S. BY- 05013 :TESTED NORM REF THE
AMM34- 22-00
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782148 14FEB ORD ACP :DUE TOREPLACEMENT OF CAPT AND F-O O2
MASK ACCOMPLISH FLIGHT INTERPHONE TEST AS REQUIRED PER 35-11-51
PAGE 407 BY- 49311 :TESTED NORM REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:35 -
»AMSDIS / 6452 / ALL/ / F / 3782145 ACFT DATA DISPLAY
3782147 14FEB ORD CON :FLT DECK SEAT COVERS NEED TO BE
REPLACED D UE TO EXCESSIVE WATER
CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT
BACK COV ER.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782146 14FEB ORD ACP :INSTALL # 2 RT CABIN WINDOW. BY- 39374
:INSTALLED # 2 RT WINDOW REF MM56-21-01. CONT OF AMIS ITEM
3782144 :RPL # 2RT WINDOW.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782143 ACFT DATA DISPLAY
3782145 14FEB ORD CON :NEED TO ACCOMPLISH OPERATION TEST OF
MAIN (LEFT ,RIGHT,CENTER) HYDRAULIC SYSTEM REFMM29-11-00 BY-
94914 :ACP TO 29-11-00 UP TO 2D N EED TO RUN ENGINES FOR
REMAINDER OF CK
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:29 -
3782144 14FEB ORD CON :INSTALL # 2 RT CABIN WINDOW. BY- 39374
:INSTALLED # 2 RT WINDOW REF MM56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782141 ACFT DATA DISPLAY
3782143 14FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF
MAIN (LEFT ,RIGHT,AND CENTER HYDRAULIC SYSTEM BY- 94914
:DUPLICATE CARD SEE SMC88
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:29 -
3782142 14FEB ORD ACP :NEED TO COMPLETEOPERATIONAL CHECK OF
ANGLE OF ATTACK PROBE HEAT(30-32-00)ANDTOTAL AIR TEMP PROBE
HEAT(30-3 3-00)AND ENGINE PROBE HEAT(30-34-00) BY- 94914
:ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
»AMSDIS / 6452 / ALL/ / F / 3782139 ACFT DATA DISPLAY
3782141 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHECK OF
TCAS (34-45-00)AND EGPWS(34-46-00) BY- 94914 :ACCOMPLISH
SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782140 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF
IRS(RE FMM34-21-00) AND EFIS(34-22-00) AND ILS(34-31-00) BY-
94914 :ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782137 ACFT DATA DISPLAY
3782139 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF
ALTITU DE ALERT SYSTEM REFMM 34-16-00 BY- 94914 :ACCOMPLISH
SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782138 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF HF
SYS TEM REFMM 23-11-00 BY- 94914 :ACCOMPLISH SUCCESSFUL CHEC K
REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782135 ACFT DATA DISPLAY
3782137 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHECK OF
VHF SYSTEMS # 1,2,3 REFMM 23-12-00 BY- 94914 :ACCOMPLISH
SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782136 14FEB ORD ADJ :ADF NEEDS OP CK REF MM34-57-00-501. BY-
05013 :ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782133 ACFT DATA DISPLAY
3782135 14FEB ORD ADJ :ILS CTL NEEDS OP CK DUE TO
REPLACEMENT,REF MM34-31-02 BY- 05013 :ACCOMPLISH SUCCESSFUL CHEC
K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782134 14FEB ORD ADJ :CAPT AND F-O CDU'S NEED OP CK DUE TO
REPLA CEMENT.REF MM34-61-02. BY- 05013 :ACCOMPLISH SUCCESSFUL
CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782131 ACFT DATA DISPLAY
3782133 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHK OF
ACARS 23-22-00 SYSTEM BY- 94914 :ACCOMPLISH SUCCESSFUL CHEC K
REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782132 14FEB ORD ADJ :NEED TO ACCOMPLISH OPERATIONAL TEST OF
WEU CARD MODULE REFMM 31-41-00 BY- 94914 :ACCOMPLISH SUCCESSFUL
CHEC K REF THE AMM31-51-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782129 ACFT DATA DISPLAY
3782131 14FEB ORD ADJ :CKPT AUDIO PANELS NEED OP CK DUE TO
REPLAC EMENT. BY- 05013 :ACCOMPLISH SUCCESSFUL CHEC K REF THE
AMM23-51-01
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782130 14FEB ORD ADJ :RUDDER TRIM IND NEEDS OP CK DUE TO
REPLACE MENT,REF MM27-28-05 BY- 05013 :ACCOMPLISH SUCCESSFUL
CHEC K REF THE AMM
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782127 ACFT DATA DISPLAY
3782129 14FEB ORD CON :FWD CARGO PIT LOAD STOP BENT IPC
25-53-13 -012 ITEM 205 PART #161-0863 ON AOG C4791 BY- 49297
:PART WRONG ORDERED 120-408 6 PRT ON AOG R3222
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:253 -
3782128 14FEB ORD ACP :CENTERRECIEVER RADIO ALTIMETER ANTENNA
HAS A DAMAGED COUPLING, DISCONNECTED FROM CABLE. BY- 49311
:REPLACED CONNECTOR D33 PER SWPM 20-51-15. NEED NEW GEL GASKET
FOR ANTENNA REINSTALLATIO N. AOM # N3078. CONT OF AMIS ITEM
3782116 :INSTALLATION OF ANTENNA
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782125 ACFT DATA DISPLAY
3782127 14FEB ORD ACP :NEED TO COMPLETE OPERATIONAL CHECK OF
MAST ER DIM AND TEST REFMM 33-16-00 BY- 94914 :ACCOMPLISHED.
TEST OK PER MM 33-16-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
3782126 14FEB ORD RPL :APU GCU WAS FAULTED WHILE ACCOMPLISHING
APU OPERATIONAL CK. REF MM24-21-00. BY- 42489 :REPLACED THE APU
GCU PER MM 24-22-02.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:24 -
»AMSDIS / 6452 / ALL/ / F / 3782123 ACFT DATA DISPLAY
3782125 14FEB ORD ACP :NEED TO ACCOMPLISH FLIGHT COMPARTMENT
ILLU MINATION CHECK REFMM33-11-00 BY- 94914 :ACCOMPLISHED. CKS
OK PER MM33-11-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:33 -
3782124 14FEB ORD ACP :NEED TO ACCOMPLISH OPERATIONAL CHECK OF
EC IAS TEST REFMM 31-41-00 BY- 94914 :ACCOMPLISHED. TEST OK PER
MM31-41-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782121 ACFT DATA DISPLAY
3782123 14FEB ORD ACP :NEED TO COMPLETE OPERATION CHECK OF FLT
DE CK WNDOW HEAT SYSTEM REFMM 30-41-00 BY- 94914 :ACCOMPLISHED.
CKS OK PER MM 30-41-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:30 -
3782122 14FEB ORD ACP :NEED TO ACCOMPLISH CARGO FIRE
OPERATIONAL TEST REFMM26-16-00 BY- 94914 :ACCOMPLISHED. TEST OK
PER MM 26-16-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
»AMSDIS / 6452 / ALL/ / F / 3782119 ACFT DATA DISPLAY
3782121 14FEB ORD ACP :NEED TO ACCOMPLISH WHEEL WELL
OPERATIONAL FIRE TEST REFMM 26-17-00 BY- 94914 :ACCOMPLISHED.
TEST OK PER MM 26-17-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
3782120 14FEB ORD ACP :NEED TO ACCOMPLISH APU OPERATIONAL FIRE
TE STREFMM 26-15-00 BY- 94914 :ACCOMPLISHED. TEST OK PER MM
26-15-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
»AMSDIS / 6452 / ALL/ / F / 3782117 ACFT DATA DISPLAY
3782119 14FEB ORD ACP :NEED TO ACCOMPLISH EGINE FIRE SYSTEM
OPERA TIONAL TEST REMM 26-11-00 BY- 94914 :ACCOMPLISHED. TEST OK
PER MM 26-11-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
3782118 14FEB ORD ACP :NEED TO ACCOMPLISH EXTERNAL POWER
OPERATIO NAL CHECK REFMM24-41-00 BY- 94914 :ACCOMPLISHED. CKS OK
PER MM 24-41-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
»AMSDIS / 6452 / ALL/ / F / 3782115 ACFT DATA DISPLAY
3782117 14FEB ORD ACP :NEED TO ACCOMPLISH DC GENERATION
OPERATION AL CHECKREFMM24-30-00 BY- 94914 :ACCOMPLISHED. CKS OK
PER MM24-30-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
3782116 14FEB ORD CON :CENTERRECIEVER RADIO ALTIMETER ANTENNA
HAS A DAMAGED COUPLING, DISCONNECTED FROM CABLE. BY- 49311
:REPLACED CONNECTOR D33 PER SWPM 20-51-15. NEED NEW GEL GASKET
FOR ANTENNA REINSTALLATIO N. AOM # N3078.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782113 ACFT DATA DISPLAY
3782115 14FEB ORD ACP :NEED TO ACCOMPLISH APU OPERATIONAL
CHECK R EFMM24-21-00 BY- 94914 :ACCOMPLISHED. OK PER MM
24-21-00.
PARTS: NONE NEEDED
INSP: MR:N POS:A ATA:49 -
3782114 14FEB ORD ACP :NEED TO ACCOMPLISH MACH TRIM
OPERATIONAL O PERATIONAL OPS CHECK BY- 94914 :ACCOMPLISHED. OK
PER MM 22-22-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:22 -
»AMSDIS / 6452 / ALL/ / F / 3782111 ACFT DATA DISPLAY
3782113 14FEB ORD ACP :NEED TO ACCOMPLISH AUTOMATIC STABILZER
TR IM OPERATION CHECKREFMM22-22-00 BY- 94914 :ACCOMPLISHED. OK
PER MM 22-22-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:22 -
3782112 14FEB ORD ACP :NEED TO ACCOMPLISH YAW DAMP OPERATIONAL
TE ST REFMM22-21-00 BY- 94914 :ACCOMPLISHED. TEST OK PER MM
22-21-00.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:22 -
»AMSDIS / 6452 / ALL/ / F / 3782110 ACFT DATA DISPLAY
3782111 14FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5
EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM
3782073 :REPLACED ALL NUTPLATES ON R-H SIDE WINDOW FRAMES FROM
STATION 511 TO 687
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782108 ACFT DATA DISPLAY
3782110 14FEB ORD SEC :OPEN P1,P2,P3 PNLS FOR ACCESS TO
INSPECT F OR WATER CONTAMINATION BY- 94914 :PANELS OPENED AND
INSPECTE D AND CLOSED NO MOISTURE FOUND.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782109 14FEB ORD RPL :DUE TO WATER CONTAMINATION. REMOVED VOR
DM E PANELS #1 MR#42233 SER# 241 AND #2 SER# 251. BY- 112802
:RPL VOR PNLS #1,#2,OP CKS OK REF MM34-51-00.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782106 ACFT DATA DISPLAY
3782108 14FEB ORD RPL :VIBRATOR ON STAND-BY ALTIMETER IS INOP.
BY- 2613 :REPLACED STAND-BY ALTIMETER - VIBRATOR NOW CHECKS
NORMAL.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:41 -
3782107 14FEB ORD RPL :TAIL SKID WARNING LITE ON FWD
INSTRUMENT PANEL DOES NOT ILLUMINATE WHEN MASTER LITE TEST
SWITCH IS PRESSED. BY- 2613 :REPLACED LITE BASE ASSY - CHECKS
NORMAL NOW WHEN TESTED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:32 -
»AMSDIS / 6452 / ALL/ / F / 3782104 ACFT DATA DISPLAY
3782106 14FEB ORD RPL :CAPT AND F-O EADI'S AND EHSI'NEED
REPLACED . BY- 05013 :RPL EADI AND EHSI'S CRTS ( 4EA).REF
MM34-22-03,MM34-22-04,OP CK TO BE ACP ON SMC 150.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
3782105 14FEB ORD RPL :EICAS UPPER AND LOWER DISPLAYS NEED
REPLAC ED. BY- 05013 :RPL UPPER AND LOWER EICAS CRT'S.OP CK TO
BE ACP ON SMC94.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782102 ACFT DATA DISPLAY
3782104 14FEB ORD RPL :ATC TRANSPONDERS NEED REPLACED. BY-
05013 :RPL LEFT AND RIGHT XPONDER S,OP CKS OK REF MM34-53-01.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
3782103 13FEB ORD OK :DUE TO WATER CONTAMINATION. REMOVED
EICAS DISPLAY SELECTOR PANEL. BY- 112802 :UNIT INSTALLED ON SEQ
3782 102,OP CK TO BE ACP ON SMC94.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782100 ACFT DATA DISPLAY
3782102 13FEB ORD RPL :DUE TO HANGER FLT DECK WATER
CONTAMINATION ECIAS DIMMER CONTROL PNL NEEDS TO BE REPLACED BY-
94914 :RPL EICAS CTL PNL.OP CK TO BE ACP ON SMC94.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:31 -
3782101 13FEB ORD OK :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED
DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2
MR23524 SER# 52 AND #3 MR 23524 SER# 22. CONT OF AMIS ITEM
3782022 :RPL 1ST OBS AUDIO PNL #3, MR RECORDED,NEEDS OP CK. CONT
OF AMIS ITEM 3782060 :DUP OP CK ITEM,OP CK TO BE ACP ON SMC146
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782098 ACFT DATA DISPLAY
3782100 13FEB ORD OK :DUE TO WATER CONTAMINATION REMOVED WX
CONT ROL PANEL MR# 43155 SER# 110. BY- 112802 :INSTALLED WXR CTL
PNL,NEED S OP CK CONT OF AMIS ITEM 3782067 :DUP OP CK ITEM,OP
CK TO BE ACP ON SMC126.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782099 13FEB ORD OK :DUE TO WATER CONTAMINATION. REMOVED
TCAS A TC CONTROL PANEL MR# 43252 SER# 331 BY- 112802 :INSTALLED
TCAS CTL PNL,NEE DS OP CK CONT OF AMIS ITEM 3782066 :DUP OP CK
ITEM,OP CK TO BE ACO ON SMC100
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782097 ACFT DATA DISPLAY
3782098 13FEB ORD RPL :ACARS CDU AND PRINTER HAS EXCESSIVE
WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED
TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED
PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED
ACARS MR# 23929 SER# 441. CONT OF AMIS ITEM 3782032 :INSTALLED
PRINTER ONLY,NEE DS OP CK CONT OF AMIS ITEM 3782065 :RPL ACARS
CDU,OP CKS FOR C DU AND PRINTER TO BE ACP ON SMC105
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782096 ACFT DATA DISPLAY
3782097 13FEB ORD OK :HF COM CONTROL PNL HAS EXTREME MOISTURE
SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914
:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.
SER# 2189. CONT OF AMIS ITEM 3782027 :INSTALLED #1&2 HF COM PNLS
.NEEDS OP CK. CONT OF AMIS ITEM 3782064 :DUP OP CK ITEM,HF OP
CK TO BE ACP ON SMC104.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782094 ACFT DATA DISPLAY
3782096 13FEB ORD SEC :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #
42127 SER# 5. CONT OF AMIS ITEM 3782023 :INSTALLED ADF PND NEEDS
SE CURED AND OP CK. CONT OF AMIS ITEM 3782062 :SECURED ADF
PNL.OP CKS DON E ON SMC146
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782095 13FEB ORD RPL :DUE TO WATER CONTAMINATION REMOVED ILS
CON TROL PANEL MR# 42263 SER# 126 BY- 112802 :RPL ILS CTL
PANEL.OP CK AC P SMC145.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782093 ACFT DATA DISPLAY
3782094 13FEB ORD RPL :CARGO FIRE TEST PANEL HAS EXCESSIVE
MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN
REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04 CONT OF AMIS
ITEM 3782015 :REMOVED DEFECTIVED FIRE TE ST PANEL. CONT OF AMIS
ITEM 3782031 :CLEANED AND REINSTALLED SA ME PNL,NO MOISTURE
NOTED,OP CK DONE ON SMC87.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
»AMSDIS / 6452 / ALL/ / F / 3782091 ACFT DATA DISPLAY
3782093 13FEB ORD RPL :NEED TO REPLACE CAPT AND F-O HANDMICS
DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED HAND MI
CS. CONT OF AMIS ITEM 3782030 :RPL CAPT AND F-O HAND MICS ,OP CK
DONE ON SMC103.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782092 13FEB ORD RPL :DUE TO WATER CONTAMINATION REMOVED ENG
FIR E CONTROL PANEL. BY- 112802 :SEE SEQ 3782091,SAME PNL
REONSTALLED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
»AMSDIS / 6452 / ALL/ / F / 3782089 ACFT DATA DISPLAY
3782091 13FEB ORD RPL :DUE TO HANGER WATER SPRAY IN FLT DECK
COVE RING PEDASTEL NEED TO INSPECT AND CLEAN ENGINE FIRE TEST
PNL. BY- 94914 :REMOVED ENG FIRE TEST PANE L. CONT OF AMIS ITEM
3782029 :CLEANED AND REINSTALLED SA ME PNL,OP CK DONE ON SMC84.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
3782090 13FEB ORD SEC :RESECURE P1,P2,AND P3 FLIGHT DECK
INDICATO R PANELS AFTER INSPECTION AND CLEANING IS COMPLETE BY-
94914 :FOUND PANELS SECURED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782088 ACFT DATA DISPLAY
3782089 13FEB ORD RPL :AIRCRAFT FLIGHT DECK PEDASTEL WAS
SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO
REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914
:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.
CONT OF AMIS ITEM 3782020 :REMOVED EHSI CONTROL PANEL S #1 MR
41835 SER# 160 AND #2 SER# 126. CONT OF AMIS ITEM 3782026 :RPL
VHF CTL PNLS 1&2,RPL E FIS CTL PNLS 1&2,OP CKS DONE ON SMC
103,SMC144.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782086 ACFT DATA DISPLAY
3782088 13FEB ORD RPL :RUDDER TRIM INDICATOR HAS WATER DAMAGE
DUE TO HANGER WATER SPRAY BY- 94914 :REMOVED DEFECTIVED PANEL
MR# 27382 SER# 42. CONT OF AMIS ITEM 3782028 :RPL RUDDER TRIM
IND,OP CK TO BE ACP ON SMC143.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:27 -
3782087 13FEB ORD RPL :DUE TO WATER CONTAMINATION AUTOPILOT
MODE CONTROL NEEDS TO BE REPLACED BY- 94914 :REPLACED ON SEQ
3782086.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:22 -
»AMSDIS / 6452 / ALL/ / F / 3782084 ACFT DATA DISPLAY
3782086 13FEB ORD RPL :DUE TO WATER CONTAMINATION REMOVED MCP
PAN EL. MR# 22137 SER# 110. BY- 112802 :RPL AUTO PILOT MCP,OP CK
T O BE ACP ON SMC76.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
3782085 13FEB ORD RPL :F-O RDDMI HAS EXCESSIVE WATER MIOSTURE
INS IDE DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED
FO RDDM I MR # 41398 SER# 72. CONT OF AMIS ITEM 3782024 :RPL
F-O RDDMI.OP CKS OK RE F MM3422-05.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782082 ACFT DATA DISPLAY
3782084 13FEB ORD RPL :DUE TO HANGAR WATER SPRAY NEED TO RE
PLACE #1 AND #2 FMC CDU'S BY- 94914 :REMOVED DEFECTIVED CDUS #1
MR 40219 SER # 121 AND #2 CDU SER #240. CONT OF AMIS ITEM
3782021 :RPL #1 AND #2 CDU'S,OP CK ACP SMC142.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
3782083 13FEB ORD CLN :DUE TO HANGER FIRE EXTINQISHER WATER
CONTA MINATION NEED TO INSPECT,CLEAN AND OPS CHK F-O OXYGEN MASK
REFMM 20-10-04 AND 35-11-00 STEP 4. BY- 94914 :REF IS BOEING
CHAPTER 20-1 0-04 CONT OF AMIS ITEM 3782016 :MASK CLEAN,NO
MOISTURE NOT ED OP CKS OK AND REPACKED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:35 -
»AMSDIS / 6452 / ALL/ / F / 3782080 ACFT DATA DISPLAY
3782082 13FEB ORD CLN :REMOVE ALL FLT DECK PEDASTEL PNLS FOR
ACCE SS TO INSPECT AND CLEAN,DRY AREA FROM WATER CONTAMINATION
BY- 94914 :INSTALLED #1 AUDIO CTL PNL ,NEEDS OP CK CONT OF AMIS
ITEM 3782068 :FOUND PANELS REMOVED,NO MO ISTURE NOTED.NOTE
AUDIO CTL PANEL OP CK TO BE ACP ON SMC141.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782081 13FEB ORD ACP :SEVERAL FLOOR PANELS REMOVED FROM FWD
CARG O COMPARTMENT TO GAIN ACCESS FOR EG1968. ( NOTE SOME
BLANKET MAT ERAIL PULLED BACK TO GAIN ACCESS) BY- 92592
:ACCOMPLISHED INSTALLATION OF FLOOR PANELS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:255 -
»AMSDIS / 6452 / ALL/ / F / 3782078 ACFT DATA DISPLAY
3782080 13FEB ORD CLN :FLT. DECK OVERHEAD CONTOL PANELS FOR
YAW D AMPER,IRU SELECTOIN,FLT ENGINES,HYDRAULICS,LIGHTS,EXTERNAL
POWER ,WINDOW HEAT,PACK CONTROL ALL NEED INSPECTING AND CLEANING
DUE T O EXCESSIVE HANGER WATER SPRAY IN FLIGHT DECKREFMM20-10-04
BY- 94914 :REF.SHOULD BOEING 20-10-04 CONT OF AMIS ITEM 3782014
:NO MOISTURE NOTED,PANELS S ECURE.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
3782079 13FEB ORD SEC :LH AND RH RECIEVER RADIO ALT ANTENNAS
ARE NOT INSTALLED. BY- 49311 :REINSTALLED LH AND RH ANTENNAS,
REF AMM 34-33-02-0401.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782076 ACFT DATA DISPLAY
3782078 13FEB ORD RPL :REF CALL OUT EG1956, REPLACE #4 RH
WINDOW. BY- 104372 :REPLACED #4 RH WINDOW REF MM56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:52 -
3782077 13FEB ORD RPL :REPLACE CABIN WINDOW #6 RIGHT PER
EG1956 CALLOUT. BY- 95722 :REPLACED CABIN WINDOW #6 R IGHT PER
MM 56-21-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782074 ACFT DATA DISPLAY
3782076 13FEB ORD OK :NEED TO COMPLETE OPERATION CHECK OF WX
RAD AR SYSTEM REFMM 34-43-00 BY- 94914 :DUPLICATE WRITE UP, WILL
B E ACCOMPLISHE ON SMC 126 PRIOR TO FLIGHT.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782075 13FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF
WX R ADAR SYSTEM (34-43-00) BY- 94914 :DUPLICATE OF WRITE UP
SMC1 26. WILL BE ACCOMPLISHED PRIOR TO FLIGHT.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782073 ACFT DATA DISPLAY
3782074 13FEB ORD ACP- :EG1958 WATER DAMAGE INSPECTION
ACCOMPLISH ALL INSPECTIONS FOR EVIDENCE OF WATER DAMAGE TO
COMPONENTS AND OR CONNECTORS PRIOR TO PUTTING POWER BACK ON THE
AIRCRAFT. MORDASIEWICZ 601 4607.
:ALL CALLED OUT INSPECTION ITEMS HAVE BEEN ACCOMPLISHED, AND
FINDINGS DOCUMENTED FOR REPAIR . OK TO APPLY POWER.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782072 ACFT DATA DISPLAY
3782073 13FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5
EA NUTPLATES AT EACH WINDOW FRAM (PARTIAL) CONT OF AMIS ITEM
3782036 :REPLACED ALL DAMAGED NUTPL ATES FOR WINDOWS AND PRIMED
AREAS. NUTPLATES FOR BLANKING PLATE S NEED INSTALL AND FLAT
BLACK PAINT APPLIED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782070 ACFT DATA DISPLAY
3782072 13FEB ORD ACP :NEED TO CLOSE UP FWD PIT SIDEWALL AND
CEIL ING PNLS OPENED UP FOR EG CALL OUT EG1969 SEQ# 3782049 BY-
108809 :ACCOMPLISHED CLOSE UP OF F WD CARGO PIT WALL AND CEILING
PANELS. RETAPED ALL SEAMS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:270 -
3782071 13FEB ORD ACP :ACCOMPLISH A GENERAL VISUAL INSPECTION
OF WINDOW FRAMES ON EFFECTED WINDOWS. BY- 70293 :ACCOMPLISHED
WINDOW FRAME EXTERNAL INSPECTION FROM STA 380RH TO STA 872RH NO
DAMAGE FOUND. INTERNAL INSPECTION NEEDS TO BE ACCOMPLISHED. CONT
OF AMIS ITEM 3782033 :NO DEFECTS NOTED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782069 ACFT DATA DISPLAY
3782070 13FEB ORD ACP- :EG1966 INSPECTION MAIN EQP CNTR
ACCOMPLISH THE FOLLOWING INSPECTION OF THE MAIN EQUIPMENT CENTER
E1 AND E2 RACKS REF MM 31.01.00. P106
ALL REMAINING ELECTRICAL AND ELECTRONIC PANELS REF MM 31.01.00
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:NO EVIDENCE OF WATER DAMAG E FOUND
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782067 ACFT DATA DISPLAY
3782069 12FEB ORD OK :VERIFY IFE FUNCTIONAL PER CSM 4.09 EX
A2C. BY- 891728 :VERIFIED IFE SYS FUNCTIONA L PER CSM 4.09 EXA2C
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782068 12FEB ORD CON :REMOVE ALL FLT DECK PEDASTEL PNLS FOR
ACCE SS TO INSPECT AND CLEAN,DRY AREA FROM WATER CONTAMINATION
BY- 94914 :INSTALLED #1 AUDIO CTL PNL ,NEEDS OP CK
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782065 ACFT DATA DISPLAY
3782067 12FEB ORD CON :DUE TO WATER CONTAMINATION REMOVED WX
CONT ROL PANEL MR# 43155 SER# 110. BY- 112802 :INSTALLED WXR CTL
PNL,NEED S OP CK
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
3782066 12FEB ORD CON :DUE TO WATER CONTAMINATION. REMOVED
TCAS A TC CONTROL PANEL MR# 43252 SER# 331 BY- 112802 :INSTALLED
TCAS CTL PNL,NEE DS OP CK
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782064 ACFT DATA DISPLAY
3782065 12FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE
WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED
TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED
PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED
ACARS MR# 23929 SER# 441. CONT OF AMIS ITEM 3782032 :INSTALLED
PRINTER ONLY,NEE DS OP CK
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782063 ACFT DATA DISPLAY
3782064 12FEB ORD CON :HF COM CONTROL PNL HAS EXTREME MOISTURE
SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914
:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.
SER# 2189. CONT OF AMIS ITEM 3782027 :INSTALLED #1&2 HF COM PNLS
.NEEDS OP CK.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782062 ACFT DATA DISPLAY
3782063 12FEB ORD ACP- :EG1967 INSPECTION FWD EQPMNT CT
ACCOMPLISH THE FOLLOWING INSPECTION OF THE FWD EQUIPMENT CENTER
WEATHER RADAR SYSTEM REF MM 34.43.00.P6
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:ACCOMPLISHED INSPECTION, FOUND NO EVIDENCE OF WATER OR FOAM
DAMAGE AT THIS TIME. SEE AMIS ITEM #3782059 FOR WEATHER RADAR TR
UNIT REPLACEMENT.
PARTS: NONE NEEDED
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782062 ACFT DATA DISPLAY
INSP: MR:N POS: ATA:31 -
ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD
»AMSDIS / 6452 / ALL/ / F / 3782061 ACFT DATA DISPLAY
3782062 12FEB ORD CON :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #
42127 SER# 5. CONT OF AMIS ITEM 3782023 :INSTALLED ADF PND
NEEDS SE CURED AND OP CK.
PARTS: NONE NEEDED
INSP: MR:F POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782060 ACFT DATA DISPLAY
3782061 12FEB ORD ACP- :EG1968 INSPECTION FWD PIT
ACCOMPLISH THE FOLLOWING INSPECTION OF THE FWD CARGO COMPARTMENT
INSPECT ALL CONNECTORS THAT ARE ATTACHED TO ALL NAVIGATIONAL
SYSTEM ANTENAS IN THIS AREA REF TO MM 34.00.00.P2
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:ACCOMPLISHED INSPECTION AND CLEANED CONNECTORS AS REQUIRED
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782059 ACFT DATA DISPLAY
3782060 12FEB ORD CON :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED
DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2
MR23524 SER# 52 AND #3 MR 23524 SER# 22. CONT OF AMIS ITEM
3782022 :RPL 1ST OBS AUDIO PNL #3, MR RECORDED,NEEDS OP CK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782058 ACFT DATA DISPLAY
3782059 12FEB ORD CON :WX RADAR T-R HAS FIRE SPRINKLER WATER
DAMA GE BY- 94914 :REPLACED WX RADAR T-R. REF MM 34-43-01-401.
PLUG AND RACK SHOW NO EVIDENCE OF FURTHER WATER DAMAGE AT THIS
TIME.THE WEATHER RADAR OPERATIONAL TEST, REF AMM 34-43-00-501
WILL NEED TO BE ACCOMPLISHED.
PARTS: NONE NEEDED
INSP: MR:O POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782057 ACFT DATA DISPLAY
3782058 12FEB ORD RPL- :EG1962 INSPECTION PILOTS OVHD P
INSPECT THE FOLLOWING FLIGHT COMPARTMENT PILOTS OVERHEAD PANELS
PILOTS AUXILIARY REF MM 31.13.16
CIRCUIT BREAKER PANELS REF MM 24.22.00
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:RPL 1ST OBS AND 2NDOBS AUD IO PANELS,SMC GENERATED FOR OP
CKS.NO MOISTURE NOTED ON OTHER P ANELS PER REF
MM31-13-16,MM24-22-00
PARTS: NONE NEEDED
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782057 ACFT DATA DISPLAY
INSP: MR:F POS: ATA:31 -
ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD
»AMSDIS / 6452 / ALL/ / F / 3782056 ACFT DATA DISPLAY
3782057 12FEB ORD CLN- :EG1972 INSPECTION PILOT RH PNL
ACCOMPLISH THE FOLLOWING INSPECTION OF THE PILOTS RIGHT SIDE
INSTRUMENT PANELS REF MM 31.01.00. P105
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:NO MOISTURD NOTED,SECURED RH PILOT PNL.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782054 ACFT DATA DISPLAY
3782056 12FEB ORD OK :DUE TO FLT DECK WATER CONTAMINATION
NEED T O INSPECT INSIDE P6 CIRCIUT BREAKER PNL BY- 94914 :NO
MOISTURE NOTED .CLOSED AND SECURED P6 PANELS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
3782055 12FEB ORD CLN :P11 OVERHEAD CIRCUIT BREAKER PANEL HAS
EXC EESIVE WATER MOISTURE DRIPPING FROM PANELS DUE HANGAR FIRE
EXTIN QISHER SPRAY IN FLT DECK BY- 94914 :NO MOISTURE
NOTED,CLOSED P 11 PANELS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
»AMSDIS / 6452 / ALL/ / F / 3782053 ACFT DATA DISPLAY
3782054 12FEB ORD CLN :DUE TO EXTREME FLT DECK PEDASTEL WATER
CON TAMINATION NEED TO CLEAN BENEATH PEDASTEL AREA FROM WATER
CONTAM INATION REFMM20-10-04 BY- 94914 :REF IS BOEING CHAPTER
20-1 0-04 CONT OF AMIS ITEM 3782019 :CLEANED CONNECTORS OF REMO
VED CTR PEDASTEL PANELS.NO MOISTURE NOTED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782052 ACFT DATA DISPLAY
3782053 12FEB ORD ACP- :EG1964 INSPECTION PAX CABIN
INSPECT THE FOLLOWING PANELS IN THE PASSANGER CABIN
FWD LIGHTING DISTRIBUTION PANEL REF MM 31.01.19
FWD ABBREVIATED ATTENDANTS PANEL REF MM 31.17.16
CABIN ATTENDANTS PANEL REF MM 31.17.11
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR
AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:ACCOMPLISHED CHECK OF PANELS. NO EVIDENCE OF WATER OR FOAM
FOUND.
PARTS: NONE NEEDED
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782052 ACFT DATA DISPLAY
INSP: MR:N POS: ATA:31 -
ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD
»AMSDIS / 6452 / ALL/ / F / 3782050 ACFT DATA DISPLAY
3782052 12FEB ORD ACP :REPLACE OR RE-INSTALL CABIN WINDOWS
EFFECT ED BY FIRE DELUGE DISCHARGE, AS NECESSARY. BY- 70293
:WILL ACCOMPLISH PER EG1956 "REPLACE WIDOW ASSEMBLIES"
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782051 12FEB ORD OK :FWD PIT SIDEWALL PANELS PEELED BACK TO
ACC ESS FLIGHT CONTROL CABLES. BY- 005936 :CABLES LUBED, CLOSE
UP COV ERED UNDER WRITE #SMC122
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
»AMSDIS / 6452 / ALL/ / F / 3782048 ACFT DATA DISPLAY
3782050 12FEB ORD OK :FWD PIT CEILING PANELS ABOVE DOOR
PEELED B ACK FOR ACCESS TO FLT CONTROL CABLES. BY- 005936
:CABLES LUBED AND CLOSUP CO VERED UNDER SMC122
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782049 12FEB ORD ACP- :EG1969 FGHT CONTROL CABLE LUBE
ACCOMPLISH LUBE OF THE FLIGHT CONTROL CABLES IN SECTION 41 AND
43 PER MM 27.00.00.P201. REFER TO MM 27.00.01 PAGE BLOCK 200 FOR
CABLE LOCATIONS. ORDLE MORDASIEWICZ 601.4607
:ACP LUBE REF 27-00-00 AND 27-00-01
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782046 ACFT DATA DISPLAY
3782048 12FEB ORD ACP- :EG1970 INSPECTION NLG
ACCOMPLISH INSPECTION AND LUBRICATION OF NLG PER MM 32.20.01
ORDLE MORDASIEWICZ 601.4607
:ACCOMPLISHED INSPECTION AN D LUBRICATION OF NLG PER MM
32-20-01.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:32 -
3782047 12FEB ORD CLN :NEED TO REPLACE CAPT AND F-O EHSI AND
EADI BY- 94914 :CLEANED AND INSPECTED NO EVIDENCE OF MOISTURE
INFILTRATION.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782044 ACFT DATA DISPLAY
3782046 12FEB ORD CLN :NEED TO REPLACE UPPER AND LOWER ECIAS
CRT' S BY- 94914 :CLEANED AND INSPECTED NO E VIDENCE OF MOISTURE
INFILTRATION.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
3782045 12FEB ORD CLN :UPPER AND LOWER ECIAS CRT'S NEED TO BE
INS PECTED FOR WATER CONTAMINATION.CLEAN OR REPLACE IF NEEDED
REFMM2 0-10-04 BY- 94914 :REF IS BOEING CHAPTER 20-1 0-04 CONT
OF AMIS ITEM 3782018 :CLEANED INSPECTED AND INST ALLED UPPER
AND LOWER EICAS SCREENS NO MOISTURE NOTED.NEED POWER FOR OPS
CHECKS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782042 ACFT DATA DISPLAY
3782044 12FEB ORD CLN :GRD PROX-FLAP OVRD SWITCH AND GRD PROX
CON FIG OVRD SWITCH NEED TO BE INSPECTED AND CLEANEC DUE TO FLT
DECK WATER CONTAMINATION REFMM20-10-04 BY- 94914 :REF IS BOEING
CHAPTER 20-1 0-04 CONT OF AMIS ITEM 3782017 :CLEANED AND
INSPECTED SWIT CHES NO MOISTURE FOUND.NEED POWER FOR OPS CHECKS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782043 12FEB ORD CLN :LE AND TE ALTERNATE FLAP SWITCHES HAVE
EXC ESSIVE MOISTURE AROUND AND IN LENS.INSPECT AND CLEAN
REF20-10-04 BY- 94914 :CLEANED AND INSPECTED NO M OISTURE
FOUND.WAITING FOR POWER FOR OPS CHECK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782041 ACFT DATA DISPLAY
3782042 12FEB ORD OK :F-O ALTERNATE SWITCHES (AIR
DATA,EFI,IRU)H AVE EXCESSIVE WATER MOISTER AROUND AND INSIDE
LENS BY- 94914 :FOUND SWITCHES DRIED OUT. WAITING FOR POWER FOR
OPS CHECK.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782040 ACFT DATA DISPLAY
3782041 12FEB ORD CLN- :EG1961 INSPECTION INSTR PANEL
INSPECT THE FOLLOWING FLIGHT COMPARTMENT INSTRUMENT PANELS
PILOTS CENTER INSTRUMENT PANEL MM 31.11.16
CAPTAINS INSTRUMENT PANEL MM.31.11.11
PILOTS AUTOMATIC FLIGHT CONTROL PANEL MM 31.11.21
FIRST OFFICER'S INSTRUMENT PANEL MM 31.11.26.
INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC
ALCOMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT
AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN
CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS
FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTO
R AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:INSPECTED ALL CONNECTORS KORRY SWITCHES AND KORRY INDICATOR
LIGHTS AND SOCKETS CLEANED WH RE NECESSARY.NO MOISTURE FOUND.
ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU
»AMSDIS / 6452 / ALL/ / F / 3782040 ACFT DATA DISPLAY
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD
»AMSDIS / 6452 / ALL/ / F / 3782039 ACFT DATA DISPLAY
3782040 12FEB ORD CLN- :EG1960 INSPECTION CNTRL STAND
INSPECT FWD ELECTRICAL PANEL MM 31.11.31 AND PILOTS CONTROL
STAND MM 31.11.41 AND AFT ELECTRONICS PANEL MM 31.11.36 FOR
EVIDENCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRICAL
COMPONENTS. IF EVIDENCE IS FOUND, REMOVE THE COMPONENT, RED TAG
IT AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR
EVIDENCE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF
WATER IS FOUND. ACCOMPLISH SYSTEM TEST FOR THE DAMAGED
COMPONENT OR CONNECTOR AS NECESSARY. ORDLE MORDASIEWICZ 601.4607
:FOUND ALL COMPONENTS REMOV ED FROM CONTROL STAND
PEDESTAL.INSPECTED AND CLEANED ALL CONNECT ORS ALL DRY AND
CLEAN.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782037 ACFT DATA DISPLAY
3782039 11FEB ORD RPL :NEED TO CLEAN CAPT AND F-O OXYGEN MASK
DUE TO FLT DECK HANGER WATER CONTAMINATION BY- 94914 :REPLACED
BOTH MASKS DUE TO WATER DAMAGE
PARTS: NONE NEEDED
INSP: MR:O POS: ATA:38 -
3782038 11FEB ORD CON :RH MID LAV NEEDS TO BE REMOVED FOR
ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:250 -
»AMSDIS / 6452 / ALL/ / F / 3782036 ACFT DATA DISPLAY
3782037 11FEB ORD ACP :ACP SURFACE EDDY CURRENT CK AROUND
REMOVED RIVETS FOR CABIN WINDOW RETAINER NUTPLATES(RT SIDE) FROM
STA 51 1 TO 775 BY- 7715 :ACP NO CRKS DETECTED AT TH IS TIME
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782035 ACFT DATA DISPLAY
3782036 11FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5
EA NUTPLATES AT EACH WINDOW FRAME STA 654+33 THRU STA 687,
REMOVED 5 EA NUTPLATE ANGLES AT STA 733 AND 775.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782034 ACFT DATA DISPLAY
3782035 11FEB ORD ACP- :EG1955 CLOSE VISUAL INSPECTION
DUE TO EXPOSURE TO HIGH PRESSURE FIRE SUPRESSION CANNON PERFORM
AN EXTERNAL CLOSE VISUAL NSPECTION OF ALL RIGHT SIDE WINDOW FRA
ME AREAS FROM STA 368 THRU STA 883.5. LOOK FOR CRACKED OR MISSIN
G PAINT, DAMAGED FASTENERS, WARPAGE, OR ANY OTHER DEFECTS.RECORD
ANY DEFECTS AND CONTACT ENGINEERING BEFORE FURTHER FLIGHT. ORDLE
MICHAEL YOURG
:ACCOMPLISHED EXTERNAL WIND OW FRAME INSPECTION FRM STA 380RH
TO STA 872RH NO DAMAGE FOUND.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:56 -
»AMSDIS / 6452 / ALL/ / F / 3782033 ACFT DATA DISPLAY
3782034 11FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN
WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES
SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT
PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA
STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES
NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA
872RH NEED TO BE CHANGED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:53 -
»AMSDIS / 6452 / ALL/ / F / 3782031 ACFT DATA DISPLAY
3782033 11FEB ORD CON :ACCOMPLISH A GENERAL VISUAL INSPECTION
OF WINDOW FRAMES ON EFFECTED WINDOWS. BY- 70293 :ACCOMPLISHED
WINDOW FRAME EXTERNAL INSPECTION FROM STA 380RH TO STA 872RH NO
DAMAGE FOUND. INTERNAL INSPECTION NEEDS TO BE ACCOMPLISHED.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782032 11FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE
WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED
TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED
PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED
ACARS MR# 23929 SER# 441.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782029 ACFT DATA DISPLAY
3782031 11FEB ORD CON :CARGO FIRE TEST PANEL HAS EXCESSIVE
MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN
REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04 CONT OF AMIS
ITEM 3782015 :REMOVED DEFECTIVED FIRE TE ST PANEL.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
3782030 11FEB ORD CON :NEED TO REPLACE CAPT AND F-O HANDMICS
DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED HAND MI
CS.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782027 ACFT DATA DISPLAY
3782029 11FEB ORD CON :DUE TO HANGER WATER SPRAY IN FLT DECK
COVE RING PEDASTEL NEED TO INSPECT AND CLEAN ENGINE FIRE TEST
PNL. BY- 94914 :REMOVED ENG FIRE TEST PANE L.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:24 -
3782028 11FEB ORD CON :RUDDER TRIM INDICATOR HAS WATER DAMAGE
DUE TO HANGER WATER SPRAY BY- 94914 :REMOVED DEFECTIVED PANEL
MR# 27382 SER# 42.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782026 ACFT DATA DISPLAY
3782027 11FEB ORD CON :HF COM CONTROL PNL HAS EXTREME MOISTURE
SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914
:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.
SER# 2189.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782025 ACFT DATA DISPLAY
3782026 11FEB ORD CON :AIRCRAFT FLIGHT DECK PEDASTEL WAS
SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO
REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914
:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.
CONT OF AMIS ITEM 3782020 :REMOVED EHSI CONTROL PANEL S #1 MR
41835 SER# 160 AND #2 SER# 126.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782023 ACFT DATA DISPLAY
3782025 11FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE
WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED
TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED
PRINTER MR# 45002 SER# 287.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782024 11FEB ORD CON :F-O RDDMI HAS EXCESSIVE WATER MIOSTURE
INS IDE DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED
FO RDDM I MR # 41398 SER# 72.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
»AMSDIS / 6452 / ALL/ / F / 3782021 ACFT DATA DISPLAY
3782023 11FEB ORD CON :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #
42127 SER# 5.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
3782022 11FEB ORD CON :DUE TO HANGAR WATER SPRAY NEED TO
REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED
DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2
MR23524 SER# 52 AND #3 MR 23524 SER# 22.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782019 ACFT DATA DISPLAY
3782021 11FEB ORD CON :DUE TO HANGAR WATER SPRAY NEED TO RE
PLACE #1 AND #2 FMC CDU'S BY- 94914 :REMOVED DEFECTIVED CDUS #1
MR 40219 SER # 121 AND #2 CDU SER #240.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782020 11FEB ORD CON :AIRCRAFT FLIGHT DECK PEDASTEL WAS
SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO
REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914
:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:23 -
»AMSDIS / 6452 / ALL/ / F / 3782017 ACFT DATA DISPLAY
3782019 11FEB ORD CON :DUE TO EXTREME FLT DECK PEDASTEL WATER
CON TAMINATION NEED TO CLEAN BENEATH PEDASTEL AREA FROM WATER
CONTAM INATION REFMM20-10-04 BY- 94914 :REF IS BOEING CHAPTER
20-1 0-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
3782018 11FEB ORD CON :UPPER AND LOWER ECIAS CRT'S NEED TO BE
INS PECTED FOR WATER CONTAMINATION.CLEAN OR REPLACE IF NEEDED
REFMM2 0-10-04 BY- 94914 :REF IS BOEING CHAPTER 20-1 0-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:31 -
»AMSDIS / 6452 / ALL/ / F / 3782015 ACFT DATA DISPLAY
3782017 11FEB ORD CON :GRD PROX-FLAP OVRD SWITCH AND GRD PROX
CON FIG OVRD SWITCH NEED TO BE INSPECTED AND CLEANEC DUE TO FLT
DECK WATER CONTAMINATION REFMM20-10-04 BY- 94914 :REF IS BOEING
CHAPTER 20-1 0-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:34 -
3782016 11FEB ORD CON :DUE TO HANGER FIRE EXTINQISHER WATER
CONTA MINATION NEED TO INSPECT,CLEAN AND OPS CHK F-O OXYGEN MASK
REFMM 20-10-04 AND 35-11-00 STEP 4. BY- 94914 :REF IS BOEING
CHAPTER 20-1 0-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:35 -
»AMSDIS / 6452 / ALL/ / F / 3782013 ACFT DATA DISPLAY
3782015 11FEB ORD CON :CARGO FIRE TEST PANEL HAS EXCESSIVE
MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN
REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:26 -
3782014 11FEB ORD CON :FLT. DECK OVERHEAD CONTOL PANELS FOR
YAW D AMPER,IRU SELECTOIN,FLT ENGINES,HYDRAULICS,LIGHTS,EXTERNAL
POWER ,WINDOW HEAT,PACK CONTROL ALL NEED INSPECTING AND CLEANING
DUE T O EXCESSIVE HANGER WATER SPRAY IN FLIGHT DECKREFMM20-10-04
BY- 94914 :REF.SHOULD BOEING 20-10-04
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:27 -
»AMSDIS / 6452 / ALL/ / F / 3782011 ACFT DATA DISPLAY
3782013 11FEB ORD CON :NEED TO REMOVED BUSINESS CLASS RIGHT
SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-
103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET.
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
3782012 10FEB ORD ACP :PANASONIC TO PULL IFE CONTROL CIRCUIT
BREAKER FOR IFE SYSTEM VISUAL INSPECTION. BY- 891728 :PULLED AND
COLLARD IFE CONTROL CIRCUIT BREAKER ON P36 PANEL FOR IFE
COMPONENT INSPECTIO N DUE TO HANGAR WATER SPRAY. PAC GRUENDER
PARTS: NONE NEEDED
INSP: MR:N POS: ATA:252 -
===============================================================
currtg/6452
»CURRTG 6452 CURRENT ROUTING RMK1: RMK2:
LOC:GSO FL: 9915/17 RMK3: STP: T/3S C/ D/
L/O FLT-DT ORG ETD ETA DST END E/TM ACC/TM 74:04
MMWRK 9915-17 GSO RLS:171619 ERTS: 162359 WRK:DF/SW/SW/LM/NA
===============================================================
olrdis//6452
»OLRDIS/ - / 6452/ 1 / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/LOG001/ /*** / ACP ETOPS SVC CHECK PER MOP 06-001-06.
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/LOG002/ /*** / EICAS MSG TE FLAP DISAGREE DISPLAYED,
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/SMC001/ /*** / DUE TOO HIGH PRESSURE FIRE SUPPRESSION CAN
/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..
/SMC002/ /*** / DUE TOO HIGH PRESSUR FIRE SUPPRESSION CANN
/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..
/SMC003/ /*** / ALL RT. SIDE BUSINESS CLASS SIDEWALLS HAVE
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/SMC004/ /*** / SERVICE OIL NBR 1 ENG. CHECK OIL QTY ON NBR
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/SMC005/ /*** / LAVATORY WASTE LEVEL SERVICE CHECK
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
===============================================================
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/LOG001/ /*** / ACP ETOPS SVC CHECK PER MOP 06-001-06.
INF: SVC ENG AND APU OIL PER MOP & VERIFY CONSUMPTION NORMAL.
REVIEW EICAS FOR O2 SVC, HYD SVC, & STATUS MSGS. CHK EQUIP COOL
MONITOR FLOW. ACP LOG REVIEW PER MOP. ACP WALK-AROUND CHECK.
REF: MOP 06-001-06 MOP 04-002-01 MOP 04-002-02
MOP 07-005-01 MRM: 99767
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP FOR MORE INFO PAGE 1 OF 7 »RU
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/LOG002/ /*** / EICAS MSG TE FLAP DISAGREE DISPLAYED,
TRAILING EDGE LIGHT ILLUM,WHEN ANY TE FLAP POSITION SELECTED.
FLAPS FAIL TO MOVE TO SELECTED POSITION. CREW COMMENTS: TE
DISAGREE AT F5 AND F25 ON GRND WHEN DIFFERENT FLAP POSIT SEL. OK
IN ALT FLAP.INTERMITTANT INF: REF MM 27-51-00,FIG105,SHT.1 MRM:
27506
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP OR DOWN FOR MORE INFO PAGE 2 OF 7 »RU »RD
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/SMC001/ /*** / DUE TOO HIGH PRESSURE FIRE SUPPRESSION CAN
NON REPLACE #1R WINDOW PLUG AND ATTACH CLIPS AND HARDWARE. BY-
70293 PROG TEXT: - ITEM ROLLED FORWARD.
/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP OR DOWN FOR MORE INFO PAGE 3 OF 7 »RU »RD
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/SMC002/ /*** / DUE TOO HIGH PRESSUR FIRE SUPPRESSION CANN
ON EXPOSURE INSPECT OR REPLACE RH OVERWING EXIT WINDOW ASSEMBLIE
S, ATTACH CLIPS AND HARWARE. REF EG1956 PTT SEQUENCE #3782213.
BY- 70293 PROG TEXT: - ITEM ROLLED FORWARD.
/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP OR DOWN FOR MORE INFO PAGE 4 OF 7 »RU »RD
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/SMC003/ /*** / ALL RT. SIDE BUSINESS CLASS SIDEWALLS HAVE
BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL
SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN
THE AFT BULK CARGO PI T. CONT OF AMIS ITEM 3782198 :WINDOW
REVEALS AND SHADES ALSO REMOVED FROM FIRST 7 PAX WINDOWS ON RH
SIDE CONT OF AMIS ITEM 3782214 PROG TEXT: - ITEM ROLLED
FORWARD.
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP OR DOWN FOR MORE INFO PAGE 5 OF 7 »RU »RD
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/SMC004/ /*** / SERVICE OIL NBR 1 ENG. CHECK OIL QTY ON NBR
2 VIA EICAS AND SVC AS REQUIRED. INF: **EICAS OIL MINIMUM
18QTS** REF: MOP 04-002-01 MRM: 97901
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-UP OR DOWN FOR MORE INFO PAGE 6 OF 7 »RU »RD
»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY
STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -
CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:
OTS: YES OILSVC DONE: NO
DO DID P NO MISSION
/SMC005/ /*** / LAVATORY WASTE LEVEL SERVICE CHECK INF:
ENSURE THAT THE FWD AND AFT WASTE TANK LEVELS ARE LESS THAN ONE
QUARTER FULL PRIOR TO DISPATCH PER LOCAL STATION PROCEDURES AND
RAMP GENERAL MANUAL 45-2-10 MRM: 97767
/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..
/DD: /OPB: /METERS: /
ROLL-DOWN FOR MORE INFO PAGE 7 OF 7 »RD

on February 28, 2009 3:52 PM | Reply
WOW, always want to take the cheapest bid. Of course this company that installed this fire EX. system is bonded? Right?? Nope?? Don't Know?
What's the Bu. Nu. on this A/C. With flight deck instrumentation requiring, extensive replacement. One may wish to avoid riding on it.
on February 28, 2009 5:55 PM | Reply
Serves them right for dumping their pension plan onto the government and all you tax payers. What goes around, comes around!
on March 2, 2009 1:24 PM | Reply
And then they sent it off to another repair station to pay big bucks for work that could have been in house by expert technicians.
One dumb mistake after another..
The company scares the crap out of me.
on March 2, 2009 4:22 PM | Reply
I can't imagine why a mechanic would stand by and smile as a window shade shatters in someone's face and an aircraft that is due to service the customers paying his check is damaged. Eastern Airlines had folks with the same though processes.
on March 2, 2009 11:16 PM | Reply
Question is ... how will You and I end up paying for this? Government bail out? 800 million will more than pay for a universal health care system, but no! .... give it to the big three banks to reward mismanagement and give out bonus money. The airlines already have my tax dollars, will they get more?
on March 3, 2009 3:43 PM | Reply
UAL board of directors deserve to be in jail for being so corrupt. Always cutting expenses in the wrong places like their employees that worked so hard to build a good company. At the end, the ESOP was a complete failure leaving us without a penny, while these assholes got big bonnuses and pay raises. Too bad the government is sleeping with these kind od parasites. We should all raise and sue the company for lost ESOP shares.
on March 3, 2009 8:05 PM | Reply
I only wish it would have happene to US Air.. They are just as deserving. LOL...
on March 4, 2009 4:09 PM | Reply
They were not laughing at shades shattering in someones face or aircraft being damaged. More like smirks as many of us realized that no matter how hard we try to make this company better it is doomed by bad upper level decision making and corporate greed.
on March 16, 2009 7:26 PM | Reply
This airline cannot make any sound decisions. It is run by insanity. They will lay you off just to rehire you within a year then lay you off and rehire you again, oh did I mention, lay you off and rehire you again . In the meantime scatter the rest of the poor souls who want to follow the insanity to other stations just to settle down and get recalled from the very same station that just laid them off. This company is EVIL and is run by evil corrupt people. Their ESOP failed. pensions failed, morale at an all time low, are not ordering any new aircrafts, dont care about their employees, this airline is a complete flop, disaster, disguisting......
on March 25, 2009 6:54 AM | Reply
I recently came across your blog and have been reading along. I thought I would leave my first comment. I don't know what to say except that I have enjoyed reading. Nice blog. I will keep visiting this blog very often.
Joannah
http://2gbmemory.net
on March 25, 2009 9:22 AM | Reply
Thanks Joannah, glad you like it. I'll try to keep posting as often as you keep looking!
on June 8, 2009 12:13 AM | Reply
I will not fly United again after reading this. Even the employees working at United don't seem to give a crap. Look at the pictures in the photograph. Then to hear that other employees are smiling as a supervisor tries to help out. If the employees don't care then I will not put myself or my family in an unsafe aircraft. Keep this up you idiots and we'll see you all in the unemployment line with the Airline out of business.
on September 13, 2009 5:20 AM | Reply
This company is falling apart. I started there in June, 2000. I left in April 2005 to work for the railroads. At least RRB is a damn good retirement!
on December 30, 2009 10:32 AM | Reply
Cutting corners...which cut back at the corner-cutter (the company in question).