United Airlines Boeing 767 trashed by firefighting system

UA 767 4.jpeg

So, the story I’m told goes like this. United takes fleet 6452, a Boeing 767-300, and gives it the full customer-facing treatment. New seats, interior fittings, and best of all, Panasonic’s all-singing, all-dancing in-flight entertainment. All done at its Chicago maintenance base.

Last week, job nearly done, the bird’s due back on the line…and then the firefighting system goes off. Allegedly for the third time in three weeks. To cut a long story short, fleet 6452 has now been patched up ready to limp off to the heavy maintenance guys at Timco to try to turn back into something rather more presentable.

Extraordinary pictures, and the worksheet for the job – which as you’ll see became a little extended – below.

Here’s the version of events passed to me:

Bay 9 and 12 ORD.

B767′s. 1,000 psi water canons take out 11 windows of a 767 – 6452.

A foreman runs up & pulls down the window shades as they shatter in his face.

Mechanics stand around and smile.

A failing company pays the lowest bidder to install a new deluge system that goes off

three times in three weeks unnecessarily.

West bay. East bay. Now…the far east bay.

Even the fire department quit stopping by as it goes off again.

They pay fire control contractors more than they pay us, but at least we gave them a quality product.

Now…they get what they pay for.

The 767′s? Probably ferry them back to TIMCO for rehab. Don’t even want to know the total cost of repairs, replacing all cockpit CRT’s etc must be big $$.  No doubt this plane will be giving us trouble down the road.



UA 767 1.jpeg






















UA 767 2.jpeg

























UA 767 3.jpeg

























UA 767 4.jpeg


























UA 767 5.jpeg


























UA 767 6.jpeg






















                                                                                                                                          »AMSDIS / 6452 / ALL/ / F / 3782220 ACFT DATA DISPLAY

BP8015                  :P RI-4  RPL BORROWED PART

REF PTT SEQ 3782163 PTT 72378 PTC 11783 DDMMMYY ORD RPL

BORROWED PART INDICATED BELOW, RMV BOROWED PART PAPER WORK (IF

ANY) FROM AC MTC BOOK. COMPLETE & ATTACH RED-STRIPE PART RMVL

TAG & ROUTE THRU STORES FOR RTN TO LENDOR. :REPLACED FO'S STAB

TRIM INDICATOR OPS CHKS GOOD.INSTALLED AMERICAN AIRLINES

PART.PN40-6 18-11 SN 012.CONTAINER PLACED IN LOB.**PAC ORDER

PLACED FOR 481-0483 OSTF# F5458 SFOLM GUZMAN**

CAT: TR: 4D MR:N MTR: CAL:Y POS: ATA:27 -

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782219 ACFT DATA DISPLAY

3782220 17FEB ORD ACP :THE ACFT HAS HAD A VISUAL INSP BY A

CERTIFIED MECHANIC OR REPAIRMAN AND THE CONTROLLER HAS

DETERMINED THAT THE ACFT IS IN A COND FOR SAFE FLIGHT FOR A TYPE

II FERRY FROM ORD TO GSO FOR REPAIR BY GSOMM WITH: INTERNAL

PASSENGER COMPARTMENT SIDEWALL PANELS ON RIGHT SIDE BUSINESS

CLASS REMOVED AND STOWED IN AFT BULK CARGO PIT. PASSENGER CABIN

WINDOW AT #1 RT AND RH OVERWING EXIT DOOR EXT INSP ACP BUT WILL

REQUIRE INTERNAL INSPECTION AND POSSIBLE RPL IN GSO.

:ACCOMPLISHED VISUAL INSP

PARTS: NONE NEEDED

INSP: MR:N POS: ATA: 000-

»AMSDIS / 6452 / ALL/ / F / 3782218 ACFT DATA DISPLAY

CF0769 17FEB ORD CF -T :P RI-1U A-C REQUIRED A CAT III DUE TO

MCP RPL'D. UNABLE TO ACCOMPLISH DUE TO CENTER A-P NOT ENGAGING.

SEE DF768. A-C DOWN GRADED TO CAT I UNTIL CAT III TEST CAN BE

ACCOMPLISHED. BY- 42489 :.

PLACARD: 9999 -

**DEFECT IDENTIFICATION** AIRCRAFT REMOVED FROM CAT II STATUS

PARTS: NONE NEEDED

AUTH: ORDMM WIATER DE CF REF: MM22-10-99 PG201

CAT:U TR: 20D MR:N MTR:AC CAL:Y POS: ATA:22 -

»AMSDIS / 6452 / ALL/ / F / 3782217 ACFT DATA DISPLAY

DF0768 17FEB ORD DF -T :P RI-1C NEED TO ACCOMPLISH AUTOPILOT AND

AUTOTHROT TLE CAT III OPERATIONAL TEST REFMM22-10-00 BY- 94914

:CENTER A-P WILL NOT ENGAGE. CURRENT FAULTS- NO INFC FCC C MCP

A-P ENG DISC AND NO INFC FCC C MCP A-P ARM IN. REPLACED MCP NO

HELP. SWAPPED FCC'S NO HELP.

PLACARD: 2210C -

DEFECT:

CENTER AUTOPILOT INOPERATIVE.

COCKPIT BREAKER(S) PULLED AND SAFETIED:

ONE OF THE FOLLOWING MAY BE PULLED:

(E17) FLT CONT CMPTR PWR L

(E20) FLT CONT CMPTR PWR C

(E35) FLT CONT CMPTR PWR R

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782215 ACFT DATA DISPLAY

3782217 17FEB ORD RPL :3RD DIGIT IN IAS-MACH WINDOW STICKS.

BY- 42489 :REPLACED MCP PER MM 22-11-02.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:22 -

3782216 17FEB ORD ACP :NEED TO PRESSURIZE AIRCRAFT TO CHECK

FOR A IR LEAKS AFTER WINDOW INSTALLATION. BY- 48312 :ACCOMPLISH

SUCCESSFUL CABI N LEAKAGE TEST REV MM05-51-24.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:21 -

»AMSDIS / 6452 / ALL/ / F / 3782213 ACFT DATA DISPLAY

3782215+17FEB ORD ACP :LAVATORY WASTE LEVEL SERVICE CHECK

:WASTE LEVEL ZERO, WATER LE VEL FULL

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:050000-01

3782214 17FEB ORD CON :ALL RT. SIDE BUSINESS CLASS SIDEWALLS

HAVE BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL

SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN

THE AFT BULK CARGO PI T. CONT OF AMIS ITEM 3782198 :WINDOW

REVEALS AND SHADES ALSO REMOVED FROM FIRST 7 PAX WINDOWS ON RH

SIDE

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782212 ACFT DATA DISPLAY

3782213 17FEB ORD ACP- :EG1956 REPLACE WINDOW ASSYS

DUE TO EXPOSURE TO HIGH PRESSURE FIRE SUPRESSION CANNON REPLACE

ALL RIGHT SIDE AIRCRAFT WINDOW ASSYS OR PLUGS, ALL SPRING ATTACH

CLIPS AND ATTACH HARDWARE FROM STA 368 THRU STA 883.5. ADDITION

ALLY REPLACE ANY DAMAGED (BENT, CRACKED, WARPED, OR PULLED) NUT

PLATE, RIVET, OR SPRING CLIP ATTACH BRACKET OR STANCION ON ALL

AFFECTED WINDOWS. RECORD ALL DEFECTS AND CONTACT ENGINEERING BEF

ORE FURTHER FLIGHT. ORDLE MICHAEL YOURG

:REPLACED RT SIDE WINDOWS, ATTACH HARDWARE AND CLIPS REF PTT

SEQUECNCE #'S 3782185, 3782184 , 3782172, 3782171, 3782192. WILL

ACCOMPLISH #1R AND OW EXITS SE PERATELY.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782211 ACFT DATA DISPLAY

DF0767 17FEB ORD DF -T :P RI-4U DUE TO WATER ENTERING INTO CABIN

AREA IN FIRST AND BUISNESS CLASS INOP THE IFE SYSTEM. BY- 99438

:IFE SYSTEM INOP.NEEDS SYST EM CHECK OF EACH SEAT.CB PULLED AND

COLLARED P36 D3

PLACARD: 2520HY -

DEFECT:

INFLIGHT ENTERTAINMENT SYSTEM INOPERATIVE.

FLIGHT CREW:

A. FLIGHT ATTENDANTS MUST PREFORM LIVE SAFETY DEMONSTRATION.

B. ADVISE PURSER.

ONBOARD SERVICES:

A. PREFORM LIVE SAFETY DEMONSTRATION.

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782211 ACFT DATA DISPLAY

CUSTOMER SERVICE:

A. CONSIDER INOPERATIVE VIDEO EQUIPMENT UNITS WHEN ASSIGNING

PASSENGERS TO FLIGHT

PARTS: NOT RECORDED

AUTH: ORDMM TALDONE J MEL REF: 2520HY

CAT:U TR:CK MR:N MTR:CIP CAL:Y POS: ATA:251 -

ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD

»AMSDIS / 6452 / ALL/ / F / 3782210 ACFT DATA DISPLAY

3782211 17FEB ORD OK :RESET C.B'S PULLED FOR HI RANGE LEAK

CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER

C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST

COMPLETE. CONT OF AMIS ITEM 3782182 :ELEVATOR FEEL TEST

ACCOMPLISHED. STARTED TO RESET CIRCUIT BREAKERS. M. ARMENTA

027552 CONT OF AMIS ITEM 3782197 :RESET C-B'S PER MM

34-11-00-503.FOUND LEFT AND RIGHT STICK SHAKER C-B'S ALREADY RES

ET.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

»AMSDIS / 6452 / ALL/ / F / 3782208 ACFT DATA DISPLAY

3782210 17FEB ORD OK :RETURN PITOT STATIC EQUIPMENT AFTER

ELEVAT OR FEEL TEST COMPLETE. BY- 05013 :RETURNED PITOT STATIC

EQUI PMENT TO TOOL ROOM.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782209 17FEB ORD OK :ELEVATOR FEEL STATIC VISCO JET DRAINS

TAPE D AND SEALED FOR PITOT STATIC TEST IN STAB COMPARTMENT,ALSO

BLAN KETS INSTALLED,REMOVE AFTER COMPUTER REPLACEMENT. BY- 05013

:REMOVED TAPE AND CAPS FROM ELEVATOR FEEL STATIC VISCO JET

DRAINS ALSO REMOVED BLANKETS AND RAGS FOUND IN STAB COMPARTMENT.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782207 ACFT DATA DISPLAY

3782208 17FEB ORD SEC :NEED TO REMOVED BUSINESS CLASS RIGHT

SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-

103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET. CONT OF AMIS

ITEM 3782013 :CLOSET REINSTALLED. NEED T O INSTALL COVER PLATE

IN LOWER FWD CUBBY HOLE. CONT OF AMIS ITEM 3782190 :SECURED

COVER PLATE IN RIG HT HAND SIDE CLOSET AND RESECURED O2 BOTTLES

IN CLOSET.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782205 ACFT DATA DISPLAY

3782207 17FEB ORD OK :REMOVE PLASTIC CAPS AND ORANGE TAPE

FROM ELEVATOR FEEL STATIC LINES, IN STAB COMPARTMENT BELOW AND

AFT OF PRESSURE BULKHEAD. BY- 42489 :REMOVED PLASTIC CAPS AND T

APE FROM ELEVATOR FEEL STATIC VISCO JET DRAINS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782206 17FEB ORD OK :P LEASE RETURN 2 EXTENTION CORDS

(K11H01), 1 ENTENTION CORD ON REEL (K05AN05) AND 4 ADAPTERS

(K09A039), THE Y ARE USED FOR FANS TO DRY THE INTERIOR OF CABIN.

BY- 92662 :RETURNED REEL KIT K05AN05 ONLY. CONT OF AMIS ITEM

3782175 :RETURNED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:05 -

»AMSDIS / 6452 / ALL/ / F / 3782203 ACFT DATA DISPLAY

3782205 17FEB ORD OK :3 EA CABIN DOOR SAFETY BARRIERS

INSTALLED NEED TO BE RETURNED TO TOOL ROOM WHEN WORK COMPLETE.

BY- 68654 :RETURNED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:52 -

3782204 17FEB ORD OK :NEED TO ACCOMPLISH OPERATION TEST OF

MAIN (LEFT ,RIGHT,CENTER) HYDRAULIC SYSTEM REFMM29-11-00 BY-

94914 :ACP TO 29-11-00 UP TO 2D N EED TO RUN ENGINES FOR

REMAINDER OF CK CONT OF AMIS ITEM 3782145 :SYSTEM OPS CHKS GOOD

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:29 -

»AMSDIS / 6452 / ALL/ / F / 3782201 ACFT DATA DISPLAY

3782203 17FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF

WING THERMAL ANTI-ICE(30-11-00)ENGINE INLET THERMAL

ANTI-ICE(30-21-0 0) BY- 94914 :SYSTEM OPS CHKS GOOD

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

3782202 17FEB ORD OK :NEED TO ACCOMPLISH AC POWER OPERATIONAL

CH ECKREFMM24-22-00 BY- 94914 :SYSTEM OPS CHKS GOOD

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

»AMSDIS / 6452 / ALL/ / F / 3782200 ACFT DATA DISPLAY

3782201 17FEB ORD ACP :RH MID LAV NEEDS TO BE REMOVED FOR

ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.

CONT OF AMIS ITEM 3782038 MAINT TEXT: CONFIG 2. :REINSTALLED

LAV, NEED TO INSTALL TOILET AND WATER LINES CONT OF AMIS ITEM

3782191 :FINISHED INSTALLATION

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:250 -

»AMSDIS / 6452 / ALL/ / F / 3782199 ACFT DATA DISPLAY

DF0766 17FEB ORD DF -T :P RI-4U ARMREST INNER SHROUD DAMAGED AT

6C BY- 02378 :NEEDS ARM COVER 021-4353 CONT OF AMIS ITEM 3782168

PLACARD: 2520MR -

DEFECT:

PASSENGER ARMREST TRAY TABLE(S) INOPERATIVE.

FLIGHT CREW:

A. ARMREST TRAY TABLE(S) RESTRICTED FROM USE AND SECURED IN

STOWED POSITION OR REMOVED.

B. ADVISE PURSER.

ONBOARD SERVICES:

A. ARMREST TRAY TABLE(S) RESTRICTED FROM USE AND SECURED IN

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782197 ACFT DATA DISPLAY

3782199 17FEB ORD ACP :INSTALL # 2 WINDOW REVEAL REF MM

56-21-01. BY- 39374 :ALL WINDOW REVEALS AND SID EWALL PANELS ARE

IN THE BULK LOADING CARGO PIT,AIRCRAFT IS TO BE FERRIED TO GSO

FOR INTERIOR REPAIR.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

3782198 17FEB ORD CON :ALL RT. SIDE BUSINESS CLASS SIDEWALLS

HAVE BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL

SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN

THE AFT BULK CARGO PI T.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782196 ACFT DATA DISPLAY

3782197 17FEB ORD CON :RESET C.B'S PULLED FOR HI RANGE LEAK

CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER

C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST

COMPLETE. CONT OF AMIS ITEM 3782182 :ELEVATOR FEEL TEST

ACCOMPLISHED. STARTED TO RESET CIRCUIT BREAKERS. M. ARMENTA

027552

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

»AMSDIS / 6452 / ALL/ / F / 3782194 ACFT DATA DISPLAY

3782196 17FEB ORD ACP :IN REF TO SMC 185 IPC REF 32-12-01-020

PAGE 4 ITEM #439 (IPC SHOW ITEM #436 WHICH IS FOR LEFT GEAR DOOR

). OLD PARTS ATTACHED TO RH MLG GEAR DOOR. BY- 97617 :INSTALLED

NEW ANGLE AND HA RDWARE.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:32 -

3782195 17FEB ORD RPL :ELEVATOR FEEL COMPUTER HAS STATIC #2

INTER NAL LEAK. BY- 05013 :REPLACED ELEVATOR FEEL COMPUTER &

ACCOMPLISHED OPS CHECK PER MM27-31-19 AND MM27-31-00. ALL OPS

CHECKS GOOD.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782192 ACFT DATA DISPLAY

3782194 17FEB ORD RPL :RH MLG DOOT TO WING FAIRING SEAL ASSY

ROB FOR ACFT 6459 OSTF S0832 U3252 BY- 94032 :REPLACED WING TO

FAIRING S EAL ASSY.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:32 -

3782193 17FEB ORD RPR :MID-LAV TOILET ASSY HAS A BROKEN LUG ON

GROUNDING WIRE WHERE IT ATTACHES TO BOWL ASSY. BY- 2613

:REPLACED LUG. M. ARMENTA 027552

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:38 -

»AMSDIS / 6452 / ALL/ / F / 3782191 ACFT DATA DISPLAY

3782192 17FEB ORD RPR :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5

EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM

3782170 :RIVETED IN NUT PLATES, INS TALLED NEW WINDOWS

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782189 ACFT DATA DISPLAY

3782191 17FEB ORD CON :RH MID LAV NEEDS TO BE REMOVED FOR

ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.

CONT OF AMIS ITEM 3782038 MAINT TEXT: CONFIG 2. :REINSTALLED

LAV, NEED TO INSTALL TOILET AND WATER LINES

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:250 -

3782190 17FEB ORD CON :NEED TO REMOVED BUSINESS CLASS RIGHT

SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-

103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET. CONT OF AMIS

ITEM 3782013 :CLOSET REINSTALLED. NEED T O INSTALL COVER PLATE

IN LOWER FWD CUBBY HOLE.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782187 ACFT DATA DISPLAY

3782189+17FEB ORD ACP :ACCOMPLISH NON-RII INSPECTION OF BY-

116614MM COMMENTS: ELEVATOR FEEL COMPUTER REPLACEMENT.

:INSPECTED ELEVATOR FEEL CO MPUTER INSTALLATION AND OPERATIONAL

CHECK PER MM27-31-17 401 AND MM27-31-00 PG567. ALL CHECKS GOOD.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:050000-01

3782188 16FEB ORD RPL :4 EACH WINDOW RETAINING CLIP BRACKETS

NEED SOLID RIVETS INSTALLED FOR RT CABIN WINDOW AT STATION 775.

BY- 2613 :AREA WITH SOLID RIVETS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782185 ACFT DATA DISPLAY

3782187 16FEB ORD RPL :2 EACH WINDOW RETAINING CLIP BRACKETS

NEED SOLID RIVETS INSTALLED FOR RT CABIN WINDOW AT STATION 733.

BY- 2613 :AREA WITH SOLID RIVETS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

3782186 16FEB ORD RPL :FLT DECK SEAT COVERS NEED TO BE

REPLACED D UE TO EXCESSIVE WATER

CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT

BACK COV ER. CONT OF AMIS ITEM 3782147 :RPLD CAPTS COVERS.STILL

NE EDS OBSERVER COVERS AOG Z4820 W5004 CONT OF AMIS ITEM 3782167

:REPLACED OBSERVER COVERS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782184 ACFT DATA DISPLAY

3782185 16FEB ORD RPL :THE PLUG WINDOWS ON RIGHT SIDE ADJACENT

TO THE CLOSET AND LAV WILL REQUIRE A MID PANE INSTALLED PRIOR TO

I NSTALLATION ALL EXISTING MID PANES ARE UNSERVICEABLE.NEW PANES

(192-1539)ARE ON AOG J3690. BY- 55690 :REF AMM 56-21-01-0401.

REINSTALLED NEW PLUG AND NEW MID PANE AT STA 787 POSITION ONLY.

CONT OF AMIS ITEM 3782174 :P LUGS INSTALLED ON RIGHT S IDE

STATION 819 & 841 ON SEQ#3782184.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782182 ACFT DATA DISPLAY

3782184 16FEB ORD RPL :REF EG1956 RPL WINDOW ASSEMBLY'S BY-

8087 :RPL WINDOW ASSEMBLY'S AND HARDWARE AT STATION'S

445,489,511,533,555,577,599,621,643,654+33

654+55,654+77,654+99,654+132,687,819 AND 841 REF AMM56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

3782183 15FEB ORD RPL :AIRPHONE CTU UNIT HAS FIRE WATER DAMAGE

BY- 94914 :RPL AIRPHONE CTU REF MM 23 -19-97.CKS OK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782180 ACFT DATA DISPLAY

3782182 15FEB ORD CON :RESET C.B'S PULLED FOR HI RANGE LEAK

CK. REF 34-11-00 PAGE 503. ALSO LEFT AND RIGHT STICK SHAKER

C.B'S. BY- 42489 :CB'S NOT RESET UNTIL AFTER ELEVATOR FEEL TEST

COMPLETE.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

3782181 15FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHK OF AIR

DA TA SYSTEM REFMM 34-13-00 BY- 94914 :OP CKS OK REF MM.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782179 ACFT DATA DISPLAY

3782180 15FEB ORD ADJ :REF EG1971, NEED TO ACCOMPLISH HI RANGE

LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO

PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489

:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.

ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2

LEAKING. ALL OTHER SYSTEMS OK. CONT OF AMIS ITEM 3782169 :THE

PREV TEXT SHOULD READ CAPT'S S2 AND R AUX S2 HAS A LEAK. CONT OF

AMIS ITEM 3782173 :FOUND ELEVATOE FEEL COMPUT ER INTERNAL

LEAK,SEE SMC 180.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782178 ACFT DATA DISPLAY

3782179 15FEB ORD ACP- :EG1971 INSPECTION PITOT STATIC

CHECK PITOT STATIC SYSTEM TO ENSURE IT IS CLEAR AND FREE OF

FOAM AND OR WATER BY PERFORMING THE FOLLOWING: ACCOMPLISH DRAIN

OF THE PITOT STATIC SYSTEM PER MM TASK 34.11.00.683.001. PERFORM

A FLUSH OF THE ALTERNATE STATIC SYSTEM PER MM TASK 34.11.00.173.

004 NOTING THAT NEITHER THE LH OR RH AIR DATA COMPUTERS NOR THE

ELEVATOR FEEL COMPUTERS PITOT STATIC LINES NEED TO BE DISCONNECT

ED TO PERFORM MM TASK 34.11.00.173.004 (ITEM 3.E.11.) FOR THE

ALTERNATE STATIC SYSTEM ONLY. ACCOMPLISH TASK 34.11.00.735.001

PITOT STATIC SYSTEM TEST. ORDLE MICHAEL YOURG

:ACP REF MM,OP CK NORMAL,NO MOISTURE NOTED,MADE ITEM FOR

ELEVATOR FEEL STATIC 2 LEAK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782176 ACFT DATA DISPLAY

3782178 15FEB ORD RPL :F-O DOME LIGHT LENS COVER IS CRACKED

DUE T O WATER PRESSURE CONTAMINATION BY- 94914 :REMOVED LIGHT

ASSY.AOG N2901 CONT OF AMIS ITEM 3782160 :INSTALLED NEW LIGHT

ASSY

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:33 -

3782177 15FEB ORD RPL :FWD CARGO PIT LOAD STOP BENT IPC

25-53-13 -012 ITEM 205 PART #161-0863 ON AOG C4791 BY- 49297

:P ART WRONG ORDERED 120-408 6 PRT ON AOG R3222 CONT OF AMIS ITEM

3782129 :REPLACED PARTIAL LOAD STOP REF MM 25-53-12-401.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:253 -

»AMSDIS / 6452 / ALL/ / F / 3782174 ACFT DATA DISPLAY

3782176 15FEB ORD ACP :2 EA DROP LIGHTS AND 2 EA EXTENSION

CORDS NEED TO BE RETURNED TO TOOL ROOM. BY- 68654 :RETURNED 2 EA

DROP LTS AND EXTENSION CORDS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

3782175 15FEB ORD CON :P LEASE RETURN 2 EXTENTION CORDS

(K11H01), 1 ENTENTION CORD ON REEL (K05AN05) AND 4 ADAPTERS

(K09A039), THE Y ARE USED FOR FANS TO DRY THE INTERIOR OF CABIN.

BY- 92662 :RETURNED REEL KIT K05AN05 ONLY.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:05 -

»AMSDIS / 6452 / ALL/ / F / 3782173 ACFT DATA DISPLAY

3782174 15FEB ORD CON :THE PLUG WINDOWS ON RIGHT SIDE ADJACENT

TO THE CLOSET AND LAV WILL REQUIRE A MID PANE INSTALLED PRIOR TO

I NSTALLATION ALL EXISTING MID PANES ARE UNSERVICEABLE.NEW PANES

(192-1539)ARE ON AOG J3690. BY- 55690 :REF AMM 56-21-01-0401.

REINSTALLED NEW PLUG AND NEW MID PANE AT STA 787 POSITION ONLY.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782172 ACFT DATA DISPLAY

3782173 15FEB ORD CON :REF EG1971, NEED TO ACCOMPLISH HI RANGE

LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO

PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489

:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.

ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2

LEAKING. ALL OTHER SYSTEMS OK. CONT OF AMIS ITEM 3782169 :THE

PREV TEXT SHOULD READ CAPT'S S2 AND R AUX S2 HAS A LEAK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782170 ACFT DATA DISPLAY

3782172 15FEB ORD RPL :RH PASSENGER WINDOW DAMAGED AT STATION

467 . BY- 101373 :INSTALLED NEW RH PASSENGER WINDOW AND HARDWARE

AT STATION 467 PER MM 56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

3782171 15FEB ORD RPL :RH PASSENGER WINDOW DAMAGED AT STATION

423 . BY- 101373 :INSTALLED NEW RH PASSENGER WINDOW AND HARDWARE

AT STATION 423 PER MM 56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782169 ACFT DATA DISPLAY

3782170 15FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5

EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM

3782111 :MANF NEW NUT PLATES AS REQ ED.INSTLED NUT PLATES

BETWEEN FRAME 733 TO 797 AS REQED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782167 ACFT DATA DISPLAY

3782169 15FEB ORD CON :REF EG1971, NEED TO ACCOMPLISH HI RANGE

LEAK CK PER MM34-11-00. ALSO INSPECT DRAINS IN E&E AND AFT CARGO

PIT AND NOSE WHEEL WELL AREA OF E&E TUNNEL. BY- 42489

:ACCOMPLISHED INPECTION OF DRAINS. ALL DRAINS FOUND TO BE DRY.

ACCOMPLISHED HI RANGE LEAK CK AND FOUND AUX STATIC SYSTEM #2

LEAKING. ALL OTHER SYSTEMS OK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782168 15FEB ORD CON :ARMREST INNER SHROUD DAMAGED AT 6C BY-

02378 :NEEDS ARM COVER 021-4353

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782165 ACFT DATA DISPLAY

3782167 15FEB ORD CON :FLT DECK SEAT COVERS NEED TO BE

REPLACED D UE TO EXCESSIVE WATER

CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT

BACK COV ER. CONT OF AMIS ITEM 3782147 :RPLD CAPTS COVERS.STILL

NE EDS OBSERVER COVERS AOG Z4820 W5004

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

CF0765 15FEB ORD CF -T :P RI-5U SEAT SHROUD AT 7H DAMAGED BY-

02378 :SHROUD OF SEAT IS PUNCTURE D NEEDS FIBERGLASS

REPAIR.PERFORMED TEMP REPAIR.

PARTS: NONE NEEDED

AUTH: ORDMM TALDONE J CF REF: MOP 05-100-01

CAT:U TR:CK MR:N MTR: CAL:Y POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782163 ACFT DATA DISPLAY

3782165 15FEB ORD OK :SIDEWALL PANELS AT SEATS 6KJ TO 10KJ

ARE TORN,CRACKED,BENT DUE TO HANGER WATER PRESSURE BLOWN THRU

WINDOW S BY- 94914 :P ANELS REMOVED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782164 15FEB ORD OK :D UE TO HANGAR FIRE EXTINQISHER WATER

SPRAY SEVERAL CABIN WINDOWS FROM SEATS 6KJ TO 10KJ WERE BLOWN

OUT BY- 94914 :WINDOW REPLACEMENT AND REPAIR COVERED UNDER

EG1956

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782161 ACFT DATA DISPLAY

3782163 15FEB ORD RPL :STAB TRIM INDICATORS HAVE EXCESSIVE

WATER DAMAGE DUE TO HANGER WATER APRAY BY- 94914 :REPLACED

CAPT'S STAB TRIM INDICATOR REF AMM27-48-06, OPS TESTED OK. F-O'S

INDICATOR NEEDS TO BE REPLACED. CONT OF AMIS ITEM 3782157

:REPLACED FO'S STAB TRIM INDICATOR OPS CHKS GOOD.INSTALLED

AMERICAN AIRLINES PART.PN40-6 18-11 SN 012.CONTAINER PLACED IN

LOB.

PARTS: NONE NEEDED

INSP: MR:B POS: ATA:27 -

3782162 15FEB ORD SVC :D RAIN AND FILL POTABLE WATER BY END OF

02- 14 BY- 070484 :D RAINED AND FILLED WATER

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:38 -

»AMSDIS / 6452 / ALL/ / F / 3782159 ACFT DATA DISPLAY

3782161 15FEB ORD SVC :D RAIN AND FILL POTABLE WATER. BY- 70293

:SERVICED WATER 2-15-09

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:38 -

3782160 15FEB ORD CON :F-O DOME LIGHT LENS COVER IS CRACKED

DUE T O WATER PRESSURE CONTAMINATION BY- 94914 :REMOVED LIGHT

ASSY.AOG N2901

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:33 -

»AMSDIS / 6452 / ALL/ / F / 3782157 ACFT DATA DISPLAY

3782159 15FEB ORD ACP :SERVICE H2O ON 02-14-09. BY- 8087

:ACCOMPLISHED THE EMPTYING AND FILLING H2O ON 2-14-09.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:38 -

3782158 14FEB ORD ACP :ALL

COMPONENTS,LIGHTS,SWITCHES,INDICATORS ON PANELS

P1-1,P1-2,P1-3,P2,P3-1,P3-2,P3-3 NEED TO OPS CHECKED WHEN

POWERED UP. BY- 139723 :OPS TESTED NORMAL. AIR DAT A INSTRUMENTS

OPS TO BE ACCOMPLISHED ON SMC 97.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782155 ACFT DATA DISPLAY

3782157 14FEB ORD CON :STAB TRIM INDICATORS HAVE EXCESSIVE

WATER DAMAGE DUE TO HANGER WATER APRAY BY- 94914 :REPLACED

CAPT'S STAB TRIM INDICATOR REF AMM27-48-06, OPS TESTED OK. F-O'S

INDICATOR NEEDS TO BE REPLACED.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:27 -

3782156 14FEB ORD ACP :1ST OBS AND 2ND OBS AUDIO SEL PANELS

REPLA CED,MR NUMBERS RECORDED,NEEDS OP CK. BY- 05013 :TESTED

NORM REF THE AMM23- 51-01

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782153 ACFT DATA DISPLAY

3782155 14FEB ORD ACP :WX RADAR T-R HAS FIRE SPRINKLER WATER

DAMA GE BY- 94914 :REPLACED WX RADAR T-R. REF MM 34-43-01-401.

PLUG AND RACK SHOW NO EVIDENCE OF FURTHER WATER DAMAGE AT THIS

TIME.THE WEATHER RADAR OPERATIONAL TEST, REF AMM 34-43-00-501

WILL NEED TO BE ACCOMPLISHED. CONT OF AMIS ITEM 3782059 :TESTED

NORM REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782154 14FEB ORD ACP :NEED TO INSPECT P87 MISC ELECTRIC EQUIP

PN L FOR WATER CONTAMINATION IN E&E BY- 94914 :INSPECTED PANEL,

NO MOISTU RE NOTED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

»AMSDIS / 6452 / ALL/ / F / 3782151 ACFT DATA DISPLAY

3782153 14FEB ORD ACP :REF EG 1964. CONNECTOR FOR EMERGENCY

EVACUATION SIGNAL PANEL ON FWD CABIN ATTENDANTS' PANEL, FWD OF

1L DOOR, WAS REMOVED AND RECONNECTED. REF MM 25-63-01-P205,

PASSENGER COMPARTMENT EMERGENCY EVACUATION SIGNAL PANEL NEEDS AN

OPERATIONAL TEST. BY- 68654 :TESTED NORM REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:251 -

3782152 14FEB ORD ACP :RADIO ALTIMETER ANTENNA TEST, REF AMM

34-33 -02-406 (E) NEEDS TO BE ACCOMPLISHED DUE TO ANTENNAS

REMOVAL AND REINSTALLATION. BY- 68654 :TESTED NORM REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782149 ACFT DATA DISPLAY

3782151 14FEB ORD ACP :NEED TO COMPLETE OPERATIONAL CHK OF PA

,CA BIN INTERPHONE,FLIGHT INTERPHONE FROM FLT DECK HANDSET REFMM

23- 31-00,23-42-00,23-51-00 BY- 94914 :TESTED NORM REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782150 14FEB ORD ACP :CAPT'S AND F-O EADI'S AND EHSI'S NEED

OP C K DUE TO REPLACEMENT,REF MM34-22-00 BY- 05013 :TESTED NORM

REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782147 ACFT DATA DISPLAY

3782149 14FEB ORD ACP :EFIS NEEDS OP CK DUE TO REPLACEMENT OF

BOT H CTL PNLS AND ALL CRT'S. BY- 05013 :TESTED NORM REF THE

AMM34- 22-00

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782148 14FEB ORD ACP :D UE TOREPLACEMENT OF CAPT AND F-O O2

MASK ACCOMPLISH FLIGHT INTERPHONE TEST AS REQUIRED PER 35-11-51

PAGE 407 BY- 49311 :TESTED NORM REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:35 -

»AMSDIS / 6452 / ALL/ / F / 3782145 ACFT DATA DISPLAY

3782147 14FEB ORD CON :FLT DECK SEAT COVERS NEED TO BE

REPLACED D UE TO EXCESSIVE WATER

CONTAMINATION(CAPT,F-O,OBSERVERS) BY- 94914 :REPLACED F-O SEAT

BACK COV ER.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782146 14FEB ORD ACP :INSTALL # 2 RT CABIN WINDOW. BY- 39374

:INSTALLED # 2 RT WINDOW REF MM56-21-01. CONT OF AMIS ITEM

3782144 :RPL # 2RT WINDOW.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782143 ACFT DATA DISPLAY

3782145 14FEB ORD CON :NEED TO ACCOMPLISH OPERATION TEST OF

MAIN (LEFT ,RIGHT,CENTER) HYDRAULIC SYSTEM REFMM29-11-00 BY-

94914 :ACP TO 29-11-00 UP TO 2D N EED TO RUN ENGINES FOR

REMAINDER OF CK

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:29 -

3782144 14FEB ORD CON :INSTALL # 2 RT CABIN WINDOW. BY- 39374

:INSTALLED # 2 RT WINDOW REF MM56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782141 ACFT DATA DISPLAY

3782143 14FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF

MAIN (LEFT ,RIGHT,AND CENTER HYDRAULIC SYSTEM BY- 94914

:D UPLICATE CARD SEE SMC88

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:29 -

3782142 14FEB ORD ACP :NEED TO COMPLETEOPERATIONAL CHECK OF

ANGLE OF ATTACK PROBE HEAT(30-32-00)ANDTOTAL AIR TEMP PROBE

HEAT(30-3 3-00)AND ENGINE PROBE HEAT(30-34-00) BY- 94914

:ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

»AMSDIS / 6452 / ALL/ / F / 3782139 ACFT DATA DISPLAY

3782141 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHECK OF

TCAS (34-45-00)AND EGPWS(34-46-00) BY- 94914 :ACCOMPLISH

SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782140 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF

IRS(RE FMM34-21-00) AND EFIS(34-22-00) AND ILS(34-31-00) BY-

94914 :ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782137 ACFT DATA DISPLAY

3782139 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF

ALTITU DE ALERT SYSTEM REFMM 34-16-00 BY- 94914 :ACCOMPLISH

SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782138 14FEB ORD ADJ :NEED TO COMPLETE OPERATION CHECK OF HF

SYS TEM REFMM 23-11-00 BY- 94914 :ACCOMPLISH SUCCESSFUL CHEC K

REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782135 ACFT DATA DISPLAY

3782137 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHECK OF

VHF SYSTEMS # 1,2,3 REFMM 23-12-00 BY- 94914 :ACCOMPLISH

SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782136 14FEB ORD ADJ :ADF NEEDS OP CK REF MM34-57-00-501. BY-

05013 :ACCOMPLISH SUCCESSFUL CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782133 ACFT DATA DISPLAY

3782135 14FEB ORD ADJ :ILS CTL NEEDS OP CK DUE TO

REPLACEMENT,REF MM34-31-02 BY- 05013 :ACCOMPLISH SUCCESSFUL CHEC

K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782134 14FEB ORD ADJ :CAPT AND F-O CDU'S NEED OP CK DUE TO

REPLA CEMENT.REF MM34-61-02. BY- 05013 :ACCOMPLISH SUCCESSFUL

CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782131 ACFT DATA DISPLAY

3782133 14FEB ORD ADJ :NEED TO COMPLETE OPERATIONAL CHK OF

ACARS 23-22-00 SYSTEM BY- 94914 :ACCOMPLISH SUCCESSFUL CHEC K

REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782132 14FEB ORD ADJ :NEED TO ACCOMPLISH OPERATIONAL TEST OF

WEU CARD MODULE REFMM 31-41-00 BY- 94914 :ACCOMPLISH SUCCESSFUL

CHEC K REF THE AMM31-51-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782129 ACFT DATA DISPLAY

3782131 14FEB ORD ADJ :CKPT AUDIO PANELS NEED OP CK DUE TO

REPLAC EMENT. BY- 05013 :ACCOMPLISH SUCCESSFUL CHEC K REF THE

AMM23-51-01

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782130 14FEB ORD ADJ :RUDDER TRIM IND NEEDS OP CK DUE TO

REPLACE MENT,REF MM27-28-05 BY- 05013 :ACCOMPLISH SUCCESSFUL

CHEC K REF THE AMM

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782127 ACFT DATA DISPLAY

3782129 14FEB ORD CON :FWD CARGO PIT LOAD STOP BENT IPC

25-53-13 -012 ITEM 205 PART #161-0863 ON AOG C4791 BY- 49297

:P ART WRONG ORDERED 120-408 6 PRT ON AOG R3222

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:253 -

3782128 14FEB ORD ACP :CENTERRECIEVER RADIO ALTIMETER ANTENNA

HAS A DAMAGED COUPLING, DISCONNECTED FROM CABLE. BY- 49311

:REPLACED CONNECTOR D33 PER SWPM 20-51-15. NEED NEW GEL GASKET

FOR ANTENNA REINSTALLATIO N. AOM # N3078. CONT OF AMIS ITEM

3782116 :INSTALLATION OF ANTENNA

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782125 ACFT DATA DISPLAY

3782127 14FEB ORD ACP :NEED TO COMPLETE OPERATIONAL CHECK OF

MAST ER DIM AND TEST REFMM 33-16-00 BY- 94914 :ACCOMPLISHED.

TEST OK PER MM 33-16-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

3782126 14FEB ORD RPL :APU GCU WAS FAULTED WHILE ACCOMPLISHING

APU OPERATIONAL CK. REF MM24-21-00. BY- 42489 :REPLACED THE APU

GCU PER MM 24-22-02.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:24 -

»AMSDIS / 6452 / ALL/ / F / 3782123 ACFT DATA DISPLAY

3782125 14FEB ORD ACP :NEED TO ACCOMPLISH FLIGHT COMPARTMENT

ILLU MINATION CHECK REFMM33-11-00 BY- 94914 :ACCOMPLISHED. CKS

OK PER MM33-11-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:33 -

3782124 14FEB ORD ACP :NEED TO ACCOMPLISH OPERATIONAL CHECK OF

EC IAS TEST REFMM 31-41-00 BY- 94914 :ACCOMPLISHED. TEST OK PER

MM31-41-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782121 ACFT DATA DISPLAY

3782123 14FEB ORD ACP :NEED TO COMPLETE OPERATION CHECK OF FLT

DE CK WNDOW HEAT SYSTEM REFMM 30-41-00 BY- 94914 :ACCOMPLISHED.

CKS OK PER MM 30-41-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:30 -

3782122 14FEB ORD ACP :NEED TO ACCOMPLISH CARGO FIRE

OPERATIONAL TEST REFMM26-16-00 BY- 94914 :ACCOMPLISHED. TEST OK

PER MM 26-16-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

»AMSDIS / 6452 / ALL/ / F / 3782119 ACFT DATA DISPLAY

3782121 14FEB ORD ACP :NEED TO ACCOMPLISH WHEEL WELL

OPERATIONAL FIRE TEST REFMM 26-17-00 BY- 94914 :ACCOMPLISHED.

TEST OK PER MM 26-17-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

3782120 14FEB ORD ACP :NEED TO ACCOMPLISH APU OPERATIONAL FIRE

TE STREFMM 26-15-00 BY- 94914 :ACCOMPLISHED. TEST OK PER MM

26-15-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

»AMSDIS / 6452 / ALL/ / F / 3782117 ACFT DATA DISPLAY

3782119 14FEB ORD ACP :NEED TO ACCOMPLISH EGINE FIRE SYSTEM

OPERA TIONAL TEST REMM 26-11-00 BY- 94914 :ACCOMPLISHED. TEST OK

PER MM 26-11-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

3782118 14FEB ORD ACP :NEED TO ACCOMPLISH EXTERNAL POWER

OPERATIO NAL CHECK REFMM24-41-00 BY- 94914 :ACCOMPLISHED. CKS OK

PER MM 24-41-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

»AMSDIS / 6452 / ALL/ / F / 3782115 ACFT DATA DISPLAY

3782117 14FEB ORD ACP :NEED TO ACCOMPLISH DC GENERATION

OPERATION AL CHECKREFMM24-30-00 BY- 94914 :ACCOMPLISHED. CKS OK

PER MM24-30-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

3782116 14FEB ORD CON :CENTERRECIEVER RADIO ALTIMETER ANTENNA

HAS A DAMAGED COUPLING, DISCONNECTED FROM CABLE. BY- 49311

:REPLACED CONNECTOR D33 PER SWPM 20-51-15. NEED NEW GEL GASKET

FOR ANTENNA REINSTALLATIO N. AOM # N3078.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782113 ACFT DATA DISPLAY

3782115 14FEB ORD ACP :NEED TO ACCOMPLISH APU OPERATIONAL

CHECK R EFMM24-21-00 BY- 94914 :ACCOMPLISHED. OK PER MM

24-21-00.

PARTS: NONE NEEDED

INSP: MR:N POS:A ATA:49 -

3782114 14FEB ORD ACP :NEED TO ACCOMPLISH MACH TRIM

OPERATIONAL O PERATIONAL OPS CHECK BY- 94914 :ACCOMPLISHED. OK

PER MM 22-22-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:22 -

»AMSDIS / 6452 / ALL/ / F / 3782111 ACFT DATA DISPLAY

3782113 14FEB ORD ACP :NEED TO ACCOMPLISH AUTOMATIC STABILZER

TR IM OPERATION CHECKREFMM22-22-00 BY- 94914 :ACCOMPLISHED. OK

PER MM 22-22-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:22 -

3782112 14FEB ORD ACP :NEED TO ACCOMPLISH YAW DAMP OPERATIONAL

TE ST REFMM22-21-00 BY- 94914 :ACCOMPLISHED. TEST OK PER MM

22-21-00.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:22 -

»AMSDIS / 6452 / ALL/ / F / 3782110 ACFT DATA DISPLAY

3782111 14FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5

EA NUTPLATES AT EACH WINDOW FRAM (PA (PARTIAL) CONT OF AMIS ITEM

3782073 :REPLACED ALL NUTPLATES ON R-H SIDE WINDOW FRAMES FROM

STATION 511 TO 687

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782108 ACFT DATA DISPLAY

3782110 14FEB ORD SEC :OPEN P1,P2,P3 PNLS FOR ACCESS TO

INSPECT F OR WATER CONTAMINATION BY- 94914 :P ANELS OPENED AND

INSPECTE D AND CLOSED NO MOISTURE FOUND.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782109 14FEB ORD RPL :D UE TO WATER CONTAMINATION. REMOVED VOR

DM E PANELS #1 MR#42233 SER# 241 AND #2 SER# 251. BY- 112802

:RPL VOR PNLS #1,#2,OP CKS OK REF MM34-51-00.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782106 ACFT DATA DISPLAY

3782108 14FEB ORD RPL :VIBRATOR ON STAND-BY ALTIMETER IS INOP.

BY- 2613 :REPLACED STAND-BY ALTIMETER - VIBRATOR NOW CHECKS

NORMAL.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:41 -

3782107 14FEB ORD RPL :TAIL SKID WARNING LITE ON FWD

INSTRUMENT PANEL DOES NOT ILLUMINATE WHEN MASTER LITE TEST

SWITCH IS PRESSED. BY- 2613 :REPLACED LITE BASE ASSY - CHECKS

NORMAL NOW WHEN TESTED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:32 -

»AMSDIS / 6452 / ALL/ / F / 3782104 ACFT DATA DISPLAY

3782106 14FEB ORD RPL :CAPT AND F-O EADI'S AND EHSI'NEED

REPLACED . BY- 05013 :RPL EADI AND EHSI'S CRTS ( 4EA).REF

MM34-22-03,MM34-22-04,OP CK TO BE ACP ON SMC 150.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

3782105 14FEB ORD RPL :EICAS UPPER AND LOWER DISPLAYS NEED

REPLAC ED. BY- 05013 :RPL UPPER AND LOWER EICAS CRT'S.OP CK TO

BE ACP ON SMC94.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782102 ACFT DATA DISPLAY

3782104 14FEB ORD RPL :ATC TRANSPONDERS NEED REPLACED. BY-

05013 :RPL LEFT AND RIGHT XPONDER S,OP CKS OK REF MM34-53-01.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

3782103 13FEB ORD OK :D UE TO WATER CONTAMINATION. REMOVED

EICAS DISPLAY SELECTOR PANEL. BY- 112802 :UNIT INSTALLED ON SEQ

3782 102,OP CK TO BE ACP ON SMC94.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782100 ACFT DATA DISPLAY

3782102 13FEB ORD RPL :D UE TO HANGER FLT DECK WATER

CONTAMINATION ECIAS DIMMER CONTROL PNL NEEDS TO BE REPLACED BY-

94914 :RPL EICAS CTL PNL.OP CK TO BE ACP ON SMC94.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:31 -

3782101 13FEB ORD OK :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED

DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2

MR23524 SER# 52 AND #3 MR 23524 SER# 22. CONT OF AMIS ITEM

3782022 :RPL 1ST OBS AUDIO PNL #3, MR RECORDED,NEEDS OP CK. CONT

OF AMIS ITEM 3782060 :D UP OP CK ITEM,OP CK TO BE ACP ON SMC146

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782098 ACFT DATA DISPLAY

3782100 13FEB ORD OK :D UE TO WATER CONTAMINATION REMOVED WX

CONT ROL PANEL MR# 43155 SER# 110. BY- 112802 :INSTALLED WXR CTL

PNL,NEED S OP CK CONT OF AMIS ITEM 3782067 :D UP OP CK ITEM,OP

CK TO BE ACP ON SMC126.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782099 13FEB ORD OK :D UE TO WATER CONTAMINATION. REMOVED

TCAS A TC CONTROL PANEL MR# 43252 SER# 331 BY- 112802 :INSTALLED

TCAS CTL PNL,NEE DS OP CK CONT OF AMIS ITEM 3782066 :D UP OP CK

ITEM,OP CK TO BE ACO ON SMC100

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782097 ACFT DATA DISPLAY

3782098 13FEB ORD RPL :ACARS CDU AND PRINTER HAS EXCESSIVE

WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED

TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED

PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED

ACARS MR# 23929 SER# 441. CONT OF AMIS ITEM 3782032 :INSTALLED

PRINTER ONLY,NEE DS OP CK CONT OF AMIS ITEM 3782065 :RPL ACARS

CDU,OP CKS FOR C DU AND PRINTER TO BE ACP ON SMC105

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782096 ACFT DATA DISPLAY

3782097 13FEB ORD OK :HF COM CONTROL PNL HAS EXTREME MOISTURE

SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914

:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.

SER# 2189. CONT OF AMIS ITEM 3782027 :INSTALLED #1&2 HF COM PNLS

.NEEDS OP CK. CONT OF AMIS ITEM 3782064 :D UP OP CK ITEM,HF OP

CK TO BE ACP ON SMC104.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782094 ACFT DATA DISPLAY

3782096 13FEB ORD SEC :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #

42127 SER# 5. CONT OF AMIS ITEM 3782023 :INSTALLED ADF PND NEEDS

SE CURED AND OP CK. CONT OF AMIS ITEM 3782062 :SECURED ADF

PNL.OP CKS DON E ON SMC146

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782095 13FEB ORD RPL :D UE TO WATER CONTAMINATION REMOVED ILS

CON TROL PANEL MR# 42263 SER# 126 BY- 112802 :RPL ILS CTL

PANEL.OP CK AC P SMC145.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782093 ACFT DATA DISPLAY

3782094 13FEB ORD RPL :CARGO FIRE TEST PANEL HAS EXCESSIVE

MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN

REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04 CONT OF AMIS

ITEM 3782015 :REMOVED DEFECTIVED FIRE TE ST PANEL. CONT OF AMIS

ITEM 3782031 :CLEANED AND REINSTALLED SA ME PNL,NO MOISTURE

NOTED,OP CK DONE ON SMC87.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

»AMSDIS / 6452 / ALL/ / F / 3782091 ACFT DATA DISPLAY

3782093 13FEB ORD RPL :NEED TO REPLACE CAPT AND F-O HANDMICS

DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED HAND MI

CS. CONT OF AMIS ITEM 3782030 :RPL CAPT AND F-O HAND MICS ,OP CK

DONE ON SMC103.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782092 13FEB ORD RPL :D UE TO WATER CONTAMINATION REMOVED ENG

FIR E CONTROL PANEL. BY- 112802 :SEE SEQ 3782091,SAME PNL

REONSTALLED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

»AMSDIS / 6452 / ALL/ / F / 3782089 ACFT DATA DISPLAY

3782091 13FEB ORD RPL :D UE TO HANGER WATER SPRAY IN FLT DECK

COVE RING PEDASTEL NEED TO INSPECT AND CLEAN ENGINE FIRE TEST

PNL. BY- 94914 :REMOVED ENG FIRE TEST PANE L. CONT OF AMIS ITEM

3782029 :CLEANED AND REINSTALLED SA ME PNL,OP CK DONE ON SMC84.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

3782090 13FEB ORD SEC :RESECURE P1,P2,AND P3 FLIGHT DECK

INDICATO R PANELS AFTER INSPECTION AND CLEANING IS COMPLETE BY-

94914 :FOUND PANELS SECURED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782088 ACFT DATA DISPLAY

3782089 13FEB ORD RPL :AIRCRAFT FLIGHT DECK PEDASTEL WAS

SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO

REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914

:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.

CONT OF AMIS ITEM 3782020 :REMOVED EHSI CONTROL PANEL S #1 MR

41835 SER# 160 AND #2 SER# 126. CONT OF AMIS ITEM 3782026 :RPL

VHF CTL PNLS 1&2,RPL E FIS CTL PNLS 1&2,OP CKS DONE ON SMC

103,SMC144.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782086 ACFT DATA DISPLAY

3782088 13FEB ORD RPL :RUDDER TRIM INDICATOR HAS WATER DAMAGE

DUE TO HANGER WATER SPRAY BY- 94914 :REMOVED DEFECTIVED PANEL

MR# 27382 SER# 42. CONT OF AMIS ITEM 3782028 :RPL RUDDER TRIM

IND,OP CK TO BE ACP ON SMC143.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:27 -

3782087 13FEB ORD RPL :D UE TO WATER CONTAMINATION AUTOPILOT

MODE CONTROL NEEDS TO BE REPLACED BY- 94914 :REPLACED ON SEQ

3782086.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:22 -

»AMSDIS / 6452 / ALL/ / F / 3782084 ACFT DATA DISPLAY

3782086 13FEB ORD RPL :D UE TO WATER CONTAMINATION REMOVED MCP

PAN EL. MR# 22137 SER# 110. BY- 112802 :RPL AUTO PILOT MCP,OP CK

T O BE ACP ON SMC76.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

3782085 13FEB ORD RPL :F-O RDDMI HAS EXCESSIVE WATER MIOSTURE

INS IDE DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED

FO RDDM I MR # 41398 SER# 72. CONT OF AMIS ITEM 3782024 :RPL

F-O RDDMI.OP CKS OK RE F MM3422-05.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782082 ACFT DATA DISPLAY

3782084 13FEB ORD RPL :D UE TO HANGAR WATER SPRAY NEED TO RE

PLACE #1 AND #2 FMC CDU'S BY- 94914 :REMOVED DEFECTIVED CDUS #1

MR 40219 SER # 121 AND #2 CDU SER #240. CONT OF AMIS ITEM

3782021 :RPL #1 AND #2 CDU'S,OP CK ACP SMC142.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

3782083 13FEB ORD CLN :D UE TO HANGER FIRE EXTINQISHER WATER

CONTA MINATION NEED TO INSPECT,CLEAN AND OPS CHK F-O OXYGEN MASK

REFMM 20-10-04 AND 35-11-00 STEP 4. BY- 94914 :REF IS BOEING

CHAPTER 20-1 0-04 CONT OF AMIS ITEM 3782016 :MASK CLEAN,NO

MOISTURE NOT ED OP CKS OK AND REPACKED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:35 -

»AMSDIS / 6452 / ALL/ / F / 3782080 ACFT DATA DISPLAY

3782082 13FEB ORD CLN :REMOVE ALL FLT DECK PEDASTEL PNLS FOR

ACCE SS TO INSPECT AND CLEAN,DRY AREA FROM WATER CONTAMINATION

BY- 94914 :INSTALLED #1 AUDIO CTL PNL ,NEEDS OP CK CONT OF AMIS

ITEM 3782068 :FOUND PANELS REMOVED,NO MO ISTURE NOTED.NOTE

AUDIO CTL PANEL OP CK TO BE ACP ON SMC141.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782081 13FEB ORD ACP :SEVERAL FLOOR PANELS REMOVED FROM FWD

CARG O COMPARTMENT TO GAIN ACCESS FOR EG1968. ( NOTE SOME

BLANKET MAT ERAIL PULLED BACK TO GAIN ACCESS) BY- 92592

:ACCOMPLISHED INSTALLATION OF FLOOR PANELS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:255 -

»AMSDIS / 6452 / ALL/ / F / 3782078 ACFT DATA DISPLAY

3782080 13FEB ORD CLN :FLT. DECK OVERHEAD CONTOL PANELS FOR

YAW D AMPER,IRU SELECTOIN,FLT ENGINES,HYDRAULICS,LIGHTS,EXTERNAL

POWER ,WINDOW HEAT,PACK CONTROL ALL NEED INSPECTING AND CLEANING

DUE T O EXCESSIVE HANGER WATER SPRAY IN FLIGHT DECKREFMM20-10-04

BY- 94914 :REF.SHOULD BOEING 20-10-04 CONT OF AMIS ITEM 3782014

:NO MOISTURE NOTED,PANELS S ECURE.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

3782079 13FEB ORD SEC :LH AND RH RECIEVER RADIO ALT ANTENNAS

ARE NOT INSTALLED. BY- 49311 :REINSTALLED LH AND RH ANTENNAS,

REF AMM 34-33-02-0401.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782076 ACFT DATA DISPLAY

3782078 13FEB ORD RPL :REF CALL OUT EG1956, REPLACE #4 RH

WINDOW. BY- 104372 :REPLACED #4 RH WINDOW REF MM56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:52 -

3782077 13FEB ORD RPL :REPLACE CABIN WINDOW #6 RIGHT PER

EG1956 CALLOUT. BY- 95722 :REPLACED CABIN WINDOW #6 R IGHT PER

MM 56-21-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782074 ACFT DATA DISPLAY

3782076 13FEB ORD OK :NEED TO COMPLETE OPERATION CHECK OF WX

RAD AR SYSTEM REFMM 34-43-00 BY- 94914 :D UPLICATE WRITE UP, WILL

B E ACCOMPLISHE ON SMC 126 PRIOR TO FLIGHT.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782075 13FEB ORD OK :NEED TO COMPLETE OPERATIONAL CHECK OF

WX R ADAR SYSTEM (34-43-00) BY- 94914 :D UPLICATE OF WRITE UP

SMC1 26. WILL BE ACCOMPLISHED PRIOR TO FLIGHT.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782073 ACFT DATA DISPLAY

3782074 13FEB ORD ACP- :EG1958 WATER DAMAGE INSPECTION

ACCOMPLISH ALL INSPECTIONS FOR EVIDENCE OF WATER DAMAGE TO

COMPONENTS AND OR CONNECTORS PRIOR TO PUTTING POWER BACK ON THE

AIRCRAFT. MORDASIEWICZ 601 4607.

:ALL CALLED OUT INSPECTION ITEMS HAVE BEEN ACCOMPLISHED, AND

FINDINGS DOCUMENTED FOR REPAIR . OK TO APPLY POWER.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782072 ACFT DATA DISPLAY

3782073 13FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5

EA NUTPLATES AT EACH WINDOW FRAM (PARTIAL) CONT OF AMIS ITEM

3782036 :REPLACED ALL DAMAGED NUTPL ATES FOR WINDOWS AND PRIMED

AREAS. NUTPLATES FOR BLANKING PLATE S NEED INSTALL AND FLAT

BLACK PAINT APPLIED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782070 ACFT DATA DISPLAY

3782072 13FEB ORD ACP :NEED TO CLOSE UP FWD PIT SIDEWALL AND

CEIL ING PNLS OPENED UP FOR EG CALL OUT EG1969 SEQ# 3782049 BY-

108809 :ACCOMPLISHED CLOSE UP OF F WD CARGO PIT WALL AND CEILING

PANELS. RETAPED ALL SEAMS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:270 -

3782071 13FEB ORD ACP :ACCOMPLISH A GENERAL VISUAL INSPECTION

OF WINDOW FRAMES ON EFFECTED WINDOWS. BY- 70293 :ACCOMPLISHED

WINDOW FRAME EXTERNAL INSPECTION FROM STA 380RH TO STA 872RH NO

DAMAGE FOUND. INTERNAL INSPECTION NEEDS TO BE ACCOMPLISHED. CONT

OF AMIS ITEM 3782033 :NO DEFECTS NOTED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782069 ACFT DATA DISPLAY

3782070 13FEB ORD ACP- :EG1966 INSPECTION MAIN EQP CNTR

ACCOMPLISH THE FOLLOWING INSPECTION OF THE MAIN EQUIPMENT CENTER

E1 AND E2 RACKS REF MM 31.01.00. P106

ALL REMAINING ELECTRICAL AND ELECTRONIC PANELS REF MM 31.01.00

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:NO EVIDENCE OF WATER DAMAG E FOUND

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782067 ACFT DATA DISPLAY

3782069 12FEB ORD OK :VERIFY IFE FUNCTIONAL PER CSM 4.09 EX

A2C. BY- 891728 :VERIFIED IFE SYS FUNCTIONA L PER CSM 4.09 EXA2C

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782068 12FEB ORD CON :REMOVE ALL FLT DECK PEDASTEL PNLS FOR

ACCE SS TO INSPECT AND CLEAN,DRY AREA FROM WATER CONTAMINATION

BY- 94914 :INSTALLED #1 AUDIO CTL PNL ,NEEDS OP CK

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782065 ACFT DATA DISPLAY

3782067 12FEB ORD CON :D UE TO WATER CONTAMINATION REMOVED WX

CONT ROL PANEL MR# 43155 SER# 110. BY- 112802 :INSTALLED WXR CTL

PNL,NEED S OP CK

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

3782066 12FEB ORD CON :D UE TO WATER CONTAMINATION. REMOVED

TCAS A TC CONTROL PANEL MR# 43252 SER# 331 BY- 112802 :INSTALLED

TCAS CTL PNL,NEE DS OP CK

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782064 ACFT DATA DISPLAY

3782065 12FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE

WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED

TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED

PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED

ACARS MR# 23929 SER# 441. CONT OF AMIS ITEM 3782032 :INSTALLED

PRINTER ONLY,NEE DS OP CK

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782063 ACFT DATA DISPLAY

3782064 12FEB ORD CON :HF COM CONTROL PNL HAS EXTREME MOISTURE

SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914

:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.

SER# 2189. CONT OF AMIS ITEM 3782027 :INSTALLED #1&2 HF COM PNLS

.NEEDS OP CK.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782062 ACFT DATA DISPLAY

3782063 12FEB ORD ACP- :EG1967 INSPECTION FWD EQPMNT CT

ACCOMPLISH THE FOLLOWING INSPECTION OF THE FWD EQUIPMENT CENTER

WEATHER RADAR SYSTEM REF MM 34.43.00.P6

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:ACCOMPLISHED INSPECTION, FOUND NO EVIDENCE OF WATER OR FOAM

DAMAGE AT THIS TIME. SEE AMIS ITEM #3782059 FOR WEATHER RADAR TR

UNIT REPLACEMENT.

PARTS: NONE NEEDED

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782062 ACFT DATA DISPLAY

INSP: MR:N POS: ATA:31 -

ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD

»AMSDIS / 6452 / ALL/ / F / 3782061 ACFT DATA DISPLAY

3782062 12FEB ORD CON :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #

42127 SER# 5. CONT OF AMIS ITEM 3782023 :INSTALLED ADF PND

NEEDS SE CURED AND OP CK.

PARTS: NONE NEEDED

INSP: MR:F POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782060 ACFT DATA DISPLAY

3782061 12FEB ORD ACP- :EG1968 INSPECTION FWD PIT

ACCOMPLISH THE FOLLOWING INSPECTION OF THE FWD CARGO COMPARTMENT

INSPECT ALL CONNECTORS THAT ARE ATTACHED TO ALL NAVIGATIONAL

SYSTEM ANTENAS IN THIS AREA REF TO MM 34.00.00.P2

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:ACCOMPLISHED INSPECTION AND CLEANED CONNECTORS AS REQUIRED

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782059 ACFT DATA DISPLAY

3782060 12FEB ORD CON :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED

DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2

MR23524 SER# 52 AND #3 MR 23524 SER# 22. CONT OF AMIS ITEM

3782022 :RPL 1ST OBS AUDIO PNL #3, MR RECORDED,NEEDS OP CK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782058 ACFT DATA DISPLAY

3782059 12FEB ORD CON :WX RADAR T-R HAS FIRE SPRINKLER WATER

DAMA GE BY- 94914 :REPLACED WX RADAR T-R. REF MM 34-43-01-401.

PLUG AND RACK SHOW NO EVIDENCE OF FURTHER WATER DAMAGE AT THIS

TIME.THE WEATHER RADAR OPERATIONAL TEST, REF AMM 34-43-00-501

WILL NEED TO BE ACCOMPLISHED.

PARTS: NONE NEEDED

INSP: MR:O POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782057 ACFT DATA DISPLAY

3782058 12FEB ORD RPL- :EG1962 INSPECTION PILOTS OVHD P

INSPECT THE FOLLOWING FLIGHT COMPARTMENT PILOTS OVERHEAD PANELS

PILOTS AUXILIARY REF MM 31.13.16

CIRCUIT BREAKER PANELS REF MM 24.22.00

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:RPL 1ST OBS AND 2NDOBS AUD IO PANELS,SMC GENERATED FOR OP

CKS.NO MOISTURE NOTED ON OTHER P ANELS PER REF

MM31-13-16,MM24-22-00

PARTS: NONE NEEDED

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782057 ACFT DATA DISPLAY

INSP: MR:F POS: ATA:31 -

ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD

»AMSDIS / 6452 / ALL/ / F / 3782056 ACFT DATA DISPLAY

3782057 12FEB ORD CLN- :EG1972 INSPECTION PILOT RH PNL

ACCOMPLISH THE FOLLOWING INSPECTION OF THE PILOTS RIGHT SIDE

INSTRUMENT PANELS REF MM 31.01.00. P105

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:NO MOISTURD NOTED,SECURED RH PILOT PNL.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782054 ACFT DATA DISPLAY

3782056 12FEB ORD OK :D UE TO FLT DECK WATER CONTAMINATION

NEED T O INSPECT INSIDE P6 CIRCIUT BREAKER PNL BY- 94914 :NO

MOISTURE NOTED .CLOSED AND SECURED P6 PANELS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

3782055 12FEB ORD CLN :P 11 OVERHEAD CIRCUIT BREAKER PANEL HAS

EXC EESIVE WATER MOISTURE DRIPPING FROM PANELS DUE HANGAR FIRE

EXTIN QISHER SPRAY IN FLT DECK BY- 94914 :NO MOISTURE

NOTED,CLOSED P 11 PANELS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

»AMSDIS / 6452 / ALL/ / F / 3782053 ACFT DATA DISPLAY

3782054 12FEB ORD CLN :D UE TO EXTREME FLT DECK PEDASTEL WATER

CON TAMINATION NEED TO CLEAN BENEATH PEDASTEL AREA FROM WATER

CONTAM INATION REFMM20-10-04 BY- 94914 :REF IS BOEING CHAPTER

20-1 0-04 CONT OF AMIS ITEM 3782019 :CLEANED CONNECTORS OF REMO

VED CTR PEDASTEL PANELS.NO MOISTURE NOTED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782052 ACFT DATA DISPLAY

3782053 12FEB ORD ACP- :EG1964 INSPECTION PAX CABIN

INSPECT THE FOLLOWING PANELS IN THE PASSANGER CABIN

FWD LIGHTING DISTRIBUTION PANEL REF MM 31.01.19

FWD ABBREVIATED ATTENDANTS PANEL REF MM 31.17.16

CABIN ATTENDANTS PANEL REF MM 31.17.11

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

AL COMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTOR

AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:ACCOMPLISHED CHECK OF PANELS. NO EVIDENCE OF WATER OR FOAM

FOUND.

PARTS: NONE NEEDED

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782052 ACFT DATA DISPLAY

INSP: MR:N POS: ATA:31 -

ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD

»AMSDIS / 6452 / ALL/ / F / 3782050 ACFT DATA DISPLAY

3782052 12FEB ORD ACP :REPLACE OR RE-INSTALL CABIN WINDOWS

EFFECT ED BY FIRE DELUGE DISCHARGE, AS NECESSARY. BY- 70293

:WILL ACCOMPLISH PER EG1956 "REPLACE WIDOW ASSEMBLIES"

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782051 12FEB ORD OK :FWD PIT SIDEWALL PANELS PEELED BACK TO

ACC ESS FLIGHT CONTROL CABLES. BY- 005936 :CABLES LUBED, CLOSE

UP COV ERED UNDER WRITE #SMC122

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

»AMSDIS / 6452 / ALL/ / F / 3782048 ACFT DATA DISPLAY

3782050 12FEB ORD OK :FWD PIT CEILING PANELS ABOVE DOOR

PEELED B ACK FOR ACCESS TO FLT CONTROL CABLES. BY- 005936

:CABLES LUBED AND CLOSUP CO VERED UNDER SMC122

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782049 12FEB ORD ACP- :EG1969 FGHT CONTROL CABLE LUBE

ACCOMPLISH LUBE OF THE FLIGHT CONTROL CABLES IN SECTION 41 AND

43 PER MM 27.00.00.P201. REFER TO MM 27.00.01 PAGE BLOCK 200 FOR

CABLE LOCATIONS. ORDLE MORDASIEWICZ 601.4607

:ACP LUBE REF 27-00-00 AND 27-00-01

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782046 ACFT DATA DISPLAY

3782048 12FEB ORD ACP- :EG1970 INSPECTION NLG

ACCOMPLISH INSPECTION AND LUBRICATION OF NLG PER MM 32.20.01

ORDLE MORDASIEWICZ 601.4607

:ACCOMPLISHED INSPECTION AN D LUBRICATION OF NLG PER MM

32-20-01.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:32 -

3782047 12FEB ORD CLN :NEED TO REPLACE CAPT AND F-O EHSI AND

EADI BY- 94914 :CLEANED AND INSPECTED NO EVIDENCE OF MOISTURE

INFILTRATION.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782044 ACFT DATA DISPLAY

3782046 12FEB ORD CLN :NEED TO REPLACE UPPER AND LOWER ECIAS

CRT' S BY- 94914 :CLEANED AND INSPECTED NO E VIDENCE OF MOISTURE

INFILTRATION.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

3782045 12FEB ORD CLN :UPPER AND LOWER ECIAS CRT'S NEED TO BE

INS PECTED FOR WATER CONTAMINATION.CLEAN OR REPLACE IF NEEDED

REFMM2 0-10-04 BY- 94914 :REF IS BOEING CHAPTER 20-1 0-04 CONT

OF AMIS ITEM 3782018 :CLEANED INSPECTED AND INST ALLED UPPER

AND LOWER EICAS SCREENS NO MOISTURE NOTED.NEED POWER FOR OPS

CHECKS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782042 ACFT DATA DISPLAY

3782044 12FEB ORD CLN :GRD PROX-FLAP OVRD SWITCH AND GRD PROX

CON FIG OVRD SWITCH NEED TO BE INSPECTED AND CLEANEC DUE TO FLT

DECK WATER CONTAMINATION REFMM20-10-04 BY- 94914 :REF IS BOEING

CHAPTER 20-1 0-04 CONT OF AMIS ITEM 3782017 :CLEANED AND

INSPECTED SWIT CHES NO MOISTURE FOUND.NEED POWER FOR OPS CHECKS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782043 12FEB ORD CLN :LE AND TE ALTERNATE FLAP SWITCHES HAVE

EXC ESSIVE MOISTURE AROUND AND IN LENS.INSPECT AND CLEAN

REF20-10-04 BY- 94914 :CLEANED AND INSPECTED NO M OISTURE

FOUND.WAITING FOR POWER FOR OPS CHECK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782041 ACFT DATA DISPLAY

3782042 12FEB ORD OK :F-O ALTERNATE SWITCHES (AIR

DATA,EFI,IRU)H AVE EXCESSIVE WATER MOISTER AROUND AND INSIDE

LENS BY- 94914 :FOUND SWITCHES DRIED OUT. WAITING FOR POWER FOR

OPS CHECK.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782040 ACFT DATA DISPLAY

3782041 12FEB ORD CLN- :EG1961 INSPECTION INSTR PANEL

INSPECT THE FOLLOWING FLIGHT COMPARTMENT INSTRUMENT PANELS

PILOTS CENTER INSTRUMENT PANEL MM 31.11.16

CAPTAINS INSTRUMENT PANEL MM.31.11.11

PILOTS AUTOMATIC FLIGHT CONTROL PANEL MM 31.11.21

FIRST OFFICER'S INSTRUMENT PANEL MM 31.11.26.

INSPECT FOR EVIDANCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRIC

ALCOMPONENTS. IF EVIDENCE IS FOUND REMOVE COMPONENT RED TAG IT

AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR EVIDEN

CE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF WATER IS

FOUND. ACCOMPLISH SYSTEM TEST FOR DAMAGED COMPONENT OR CONNECTO

R AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:INSPECTED ALL CONNECTORS KORRY SWITCHES AND KORRY INDICATOR

LIGHTS AND SOCKETS CLEANED WH RE NECESSARY.NO MOISTURE FOUND.

ROLL-UP FOR MORE INFO PAGE 1 OF 2 »RU

»AMSDIS / 6452 / ALL/ / F / 3782040 ACFT DATA DISPLAY

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

ROLL-DOWN FOR MORE INFO PAGE 2 OF 2 »RD

»AMSDIS / 6452 / ALL/ / F / 3782039 ACFT DATA DISPLAY

3782040 12FEB ORD CLN- :EG1960 INSPECTION CNTRL STAND

INSPECT FWD ELECTRICAL PANEL MM 31.11.31 AND PILOTS CONTROL

STAND MM 31.11.41 AND AFT ELECTRONICS PANEL MM 31.11.36 FOR

EVIDENCE OF WATER AND OR FOAM DAMAGE TO ALL ELECTRICAL

COMPONENTS. IF EVIDENCE IS FOUND, REMOVE THE COMPONENT, RED TAG

IT AND QUARANTINE THE ITEM. INSPECT COMPONENT CONNECTORS FOR

EVIDENCE OF WATER AND OR FOAM. DRY CONNECTORS IF EVIDENCE OF

WATER IS FOUND. ACCOMPLISH SYSTEM TEST FOR THE DAMAGED

COMPONENT OR CONNECTOR AS NECESSARY. ORDLE MORDASIEWICZ 601.4607

:FOUND ALL COMPONENTS REMOV ED FROM CONTROL STAND

PEDESTAL.INSPECTED AND CLEANED ALL CONNECT ORS ALL DRY AND

CLEAN.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782037 ACFT DATA DISPLAY

3782039 11FEB ORD RPL :NEED TO CLEAN CAPT AND F-O OXYGEN MASK

DUE TO FLT DECK HANGER WATER CONTAMINATION BY- 94914 :REPLACED

BOTH MASKS DUE TO WATER DAMAGE

PARTS: NONE NEEDED

INSP: MR:O POS: ATA:38 -

3782038 11FEB ORD CON :RH MID LAV NEEDS TO BE REMOVED FOR

ACCESS TO WINDOWS. BY- 68654 :REMOVED LAV. REF AMM25-41- 03-401.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:250 -

»AMSDIS / 6452 / ALL/ / F / 3782036 ACFT DATA DISPLAY

3782037 11FEB ORD ACP :ACP SURFACE EDDY CURRENT CK AROUND

REMOVED RIVETS FOR CABIN WINDOW RETAINER NUTPLATES(RT SIDE) FROM

STA 51 1 TO 775 BY- 7715 :ACP NO CRKS DETECTED AT TH IS TIME

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782035 ACFT DATA DISPLAY

3782036 11FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED. CONT OF AMIS ITEM 3782034 :REMOVED 5

EA NUTPLATES AT EACH WINDOW FRAME STA 654+33 THRU STA 687,

REMOVED 5 EA NUTPLATE ANGLES AT STA 733 AND 775.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782034 ACFT DATA DISPLAY

3782035 11FEB ORD ACP- :EG1955 CLOSE VISUAL INSPECTION

DUE TO EXPOSURE TO HIGH PRESSURE FIRE SUPRESSION CANNON PERFORM

AN EXTERNAL CLOSE VISUAL NSPECTION OF ALL RIGHT SIDE WINDOW FRA

ME AREAS FROM STA 368 THRU STA 883.5. LOOK FOR CRACKED OR MISSIN

G PAINT, DAMAGED FASTENERS, WARPAGE, OR ANY OTHER DEFECTS.RECORD

ANY DEFECTS AND CONTACT ENGINEERING BEFORE FURTHER FLIGHT. ORDLE

MICHAEL YOURG

:ACCOMPLISHED EXTERNAL WIND OW FRAME INSPECTION FRM STA 380RH

TO STA 872RH NO DAMAGE FOUND.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:56 -

»AMSDIS / 6452 / ALL/ / F / 3782033 ACFT DATA DISPLAY

3782034 11FEB ORD CON :EACH AFFECTED BUSINESS CLASS CABIN

WINDOW FRAME HAS NUMEROUS RETAINING CLIP NUTPLATES OR NUTPLATES

SUPPORT ANGLES THAT HAVE BEEN DAMAGED. BY- 02378 :REMOVED NUT

PLATES AT FOL LWING WINDOWS**1EA STA511RH,3EA STA 555RH,5EA

STA577RH,4EA STA 599RH,4EA STA621RH,4EA STA643 RH.NEW NUT PLATES

NEED TO BE INSTA LLED.DAMAGED NUT PLATES FROM STA654+33RH TO STA

872RH NEED TO BE CHANGED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:53 -

»AMSDIS / 6452 / ALL/ / F / 3782031 ACFT DATA DISPLAY

3782033 11FEB ORD CON :ACCOMPLISH A GENERAL VISUAL INSPECTION

OF WINDOW FRAMES ON EFFECTED WINDOWS. BY- 70293 :ACCOMPLISHED

WINDOW FRAME EXTERNAL INSPECTION FROM STA 380RH TO STA 872RH NO

DAMAGE FOUND. INTERNAL INSPECTION NEEDS TO BE ACCOMPLISHED.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782032 11FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE

WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED

TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED

PRINTER MR# 45002 SER# 287. CONT OF AMIS ITEM 3782025 :REMOVED

ACARS MR# 23929 SER# 441.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782029 ACFT DATA DISPLAY

3782031 11FEB ORD CON :CARGO FIRE TEST PANEL HAS EXCESSIVE

MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN

REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04 CONT OF AMIS

ITEM 3782015 :REMOVED DEFECTIVED FIRE TE ST PANEL.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

3782030 11FEB ORD CON :NEED TO REPLACE CAPT AND F-O HANDMICS

DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED HAND MI

CS.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782027 ACFT DATA DISPLAY

3782029 11FEB ORD CON :D UE TO HANGER WATER SPRAY IN FLT DECK

COVE RING PEDASTEL NEED TO INSPECT AND CLEAN ENGINE FIRE TEST

PNL. BY- 94914 :REMOVED ENG FIRE TEST PANE L.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:24 -

3782028 11FEB ORD CON :RUDDER TRIM INDICATOR HAS WATER DAMAGE

DUE TO HANGER WATER SPRAY BY- 94914 :REMOVED DEFECTIVED PANEL

MR# 27382 SER# 42.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782026 ACFT DATA DISPLAY

3782027 11FEB ORD CON :HF COM CONTROL PNL HAS EXTREME MOISTURE

SH OWING IN LENS SCREEN ON PEDASTAL AND OVERHEAD PNL BY- 94914

:REMOVED DEFECTIVED HF PANE L #1 MR# 23146 SER # 92 AND #2 MNF.

SER# 2189.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782025 ACFT DATA DISPLAY

3782026 11FEB ORD CON :AIRCRAFT FLIGHT DECK PEDASTEL WAS

SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO

REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914

:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.

CONT OF AMIS ITEM 3782020 :REMOVED EHSI CONTROL PANEL S #1 MR

41835 SER# 160 AND #2 SER# 126.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782023 ACFT DATA DISPLAY

3782025 11FEB ORD CON :ACARS CDU AND PRINTER HAS EXCESSIVE

WATER CONTAMINATION DUE TO HANGER WATER SPRAY IN FLT DECK,NEED

TO REPL ACE ACARS CDU AND PRINTER BY- 94914 :REMOVED DEFECTIVED

PRINTER MR# 45002 SER# 287.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782024 11FEB ORD CON :F-O RDDMI HAS EXCESSIVE WATER MIOSTURE

INS IDE DUE TO WATER CONTAMINATION BY- 94914 :REMOVED DEFECTIVED

FO RDDM I MR # 41398 SER# 72.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

»AMSDIS / 6452 / ALL/ / F / 3782021 ACFT DATA DISPLAY

3782023 11FEB ORD CON :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ADF CONTROL PNL BY- 94914 :REMOVED DEFECTIVED ADF MR #

42127 SER# 5.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

3782022 11FEB ORD CON :D UE TO HANGAR WATER SPRAY NEED TO

REPLACE ALL THREE AUDIO SELECTOR PNLS BY- 94914 :REMOVED

DEFECTIVED AUDIO S ELECTOR PANELS . #1 MR 23524 SR# 278. #2

MR23524 SER# 52 AND #3 MR 23524 SER# 22.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782019 ACFT DATA DISPLAY

3782021 11FEB ORD CON :D UE TO HANGAR WATER SPRAY NEED TO RE

PLACE #1 AND #2 FMC CDU'S BY- 94914 :REMOVED DEFECTIVED CDUS #1

MR 40219 SER # 121 AND #2 CDU SER #240.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782020 11FEB ORD CON :AIRCRAFT FLIGHT DECK PEDASTEL WAS

SPRAYED HEAVILY WITH HANGER FIRE EXTINQISHER WATER.NEED TO

REPLACE VHF # 1 AND #2 COMM PNLS,NAV PNLS,EHSI PNLS BY- 94914

:REMOVED DEFECTIVED VHF #1 MR23225 SER#78 AND VHF #2 SER 48.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:23 -

»AMSDIS / 6452 / ALL/ / F / 3782017 ACFT DATA DISPLAY

3782019 11FEB ORD CON :D UE TO EXTREME FLT DECK PEDASTEL WATER

CON TAMINATION NEED TO CLEAN BENEATH PEDASTEL AREA FROM WATER

CONTAM INATION REFMM20-10-04 BY- 94914 :REF IS BOEING CHAPTER

20-1 0-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

3782018 11FEB ORD CON :UPPER AND LOWER ECIAS CRT'S NEED TO BE

INS PECTED FOR WATER CONTAMINATION.CLEAN OR REPLACE IF NEEDED

REFMM2 0-10-04 BY- 94914 :REF IS BOEING CHAPTER 20-1 0-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:31 -

»AMSDIS / 6452 / ALL/ / F / 3782015 ACFT DATA DISPLAY

3782017 11FEB ORD CON :GRD PROX-FLAP OVRD SWITCH AND GRD PROX

CON FIG OVRD SWITCH NEED TO BE INSPECTED AND CLEANEC DUE TO FLT

DECK WATER CONTAMINATION REFMM20-10-04 BY- 94914 :REF IS BOEING

CHAPTER 20-1 0-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:34 -

3782016 11FEB ORD CON :D UE TO HANGER FIRE EXTINQISHER WATER

CONTA MINATION NEED TO INSPECT,CLEAN AND OPS CHK F-O OXYGEN MASK

REFMM 20-10-04 AND 35-11-00 STEP 4. BY- 94914 :REF IS BOEING

CHAPTER 20-1 0-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:35 -

»AMSDIS / 6452 / ALL/ / F / 3782013 ACFT DATA DISPLAY

3782015 11FEB ORD CON :CARGO FIRE TEST PANEL HAS EXCESSIVE

MOISTU RE INSIDE LENS SWITCHES,NEED TO INSPECT AND CLEAN

REFMM20-10-04 BY- 94914 :REF IS BOEING 20-10-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:26 -

3782014 11FEB ORD CON :FLT. DECK OVERHEAD CONTOL PANELS FOR

YAW D AMPER,IRU SELECTOIN,FLT ENGINES,HYDRAULICS,LIGHTS,EXTERNAL

POWER ,WINDOW HEAT,PACK CONTROL ALL NEED INSPECTING AND CLEANING

DUE T O EXCESSIVE HANGER WATER SPRAY IN FLIGHT DECKREFMM20-10-04

BY- 94914 :REF.SHOULD BOEING 20-10-04

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:27 -

»AMSDIS / 6452 / ALL/ / F / 3782011 ACFT DATA DISPLAY

3782013 11FEB ORD CON :NEED TO REMOVED BUSINESS CLASS RIGHT

SIDE CLOSET TO GAIN ACCESS TO WINDOW PANEL FOR INSPECTION. BY-

103264 :REMOVED BUSINESS CLASS RIG HT SIDE CLOSET.

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

3782012 10FEB ORD ACP :P ANASONIC TO PULL IFE CONTROL CIRCUIT

BREAKER FOR IFE SYSTEM VISUAL INSPECTION. BY- 891728 :P ULLED AND

COLLARD IFE CONTROL CIRCUIT BREAKER ON P36 PANEL FOR IFE

COMPONENT INSPECTIO N DUE TO HANGAR WATER SPRAY. PAC GRUENDER

PARTS: NONE NEEDED

INSP: MR:N POS: ATA:252 -

===============================================================

currtg/6452

»CURRTG 6452 CURRENT ROUTING RMK1: RMK2:

LOC:GSO FL: 9915/17 RMK3: STP: T/3S C/ D/

L/O FLT-DT ORG ETD ETA DST END E/TM ACC/TM 74:04

MMWRK 9915-17 GSO RLS:171619 ERTS: 162359 WRK:DF/SW/SW/LM/NA

===============================================================

olrdis//6452

»OLRDIS/ - / 6452/ 1 / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/LOG001/ /*** / ACP ETOPS SVC CHECK PER MOP 06-001-06.

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/LOG002/ /*** / EICAS MSG TE FLAP DISAGREE DISPLAYED,

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/SMC001/ /*** / DUE TOO HIGH PRESSURE FIRE SUPPRESSION CAN

/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..

/SMC002/ /*** / DUE TOO HIGH PRESSUR FIRE SUPPRESSION CANN

/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..

/SMC003/ /*** / ALL RT. SIDE BUSINESS CLASS SIDEWALLS HAVE

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/SMC004/ /*** / SERVICE OIL NBR 1 ENG. CHECK OIL QTY ON NBR

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/SMC005/ /*** / LAVATORY WASTE LEVEL SERVICE CHECK

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

===============================================================

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/LOG001/ /*** / ACP ETOPS SVC CHECK PER MOP 06-001-06.

INF: SVC ENG AND APU OIL PER MOP & VERIFY CONSUMPTION NORMAL.

REVIEW EICAS FOR O2 SVC, HYD SVC, & STATUS MSGS. CHK EQUIP COOL

MONITOR FLOW. ACP LOG REVIEW PER MOP. ACP WALK-AROUND CHECK.

REF: MOP 06-001-06 MOP 04-002-01 MOP 04-002-02

MOP 07-005-01 MRM: 99767

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP FOR MORE INFO PAGE 1 OF 7 »RU

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/LOG002/ /*** / EICAS MSG TE FLAP DISAGREE DISPLAYED,

TRAILING EDGE LIGHT ILLUM,WHEN ANY TE FLAP POSITION SELECTED.

FLAPS FAIL TO MOVE TO SELECTED POSITION. CREW COMMENTS: TE

DISAGREE AT F5 AND F25 ON GRND WHEN DIFFERENT FLAP POSIT SEL. OK

IN ALT FLAP.INTERMITTANT INF: REF MM 27-51-00,FIG105,SHT.1 MRM:

27506

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP OR DOWN FOR MORE INFO PAGE 2 OF 7 »RU »RD

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/SMC001/ /*** / DUE TOO HIGH PRESSURE FIRE SUPPRESSION CAN

NON REPLACE #1R WINDOW PLUG AND ATTACH CLIPS AND HARDWARE. BY-

70293 PROG TEXT: - ITEM ROLLED FORWARD.

/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP OR DOWN FOR MORE INFO PAGE 3 OF 7 »RU »RD

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/SMC002/ /*** / DUE TOO HIGH PRESSUR FIRE SUPPRESSION CANN

ON EXPOSURE INSPECT OR REPLACE RH OVERWING EXIT WINDOW ASSEMBLIE

S, ATTACH CLIPS AND HARWARE. REF EG1956 PTT SEQUENCE #3782213.

BY- 70293 PROG TEXT: - ITEM ROLLED FORWARD.

/DF: /CF: /PC: ...../SDR: N/MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP OR DOWN FOR MORE INFO PAGE 4 OF 7 »RU »RD

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/SMC003/ /*** / ALL RT. SIDE BUSINESS CLASS SIDEWALLS HAVE

BEEN REMOVED FOR DAMAGE OR TO ACCESS DAMAGE BY- 02378 :ALL

SIDEWALL PANELS WIDOW REVEALS AND MISC ITEMS HAVE BEEN PLACED IN

THE AFT BULK CARGO PI T. CONT OF AMIS ITEM 3782198 :WINDOW

REVEALS AND SHADES ALSO REMOVED FROM FIRST 7 PAX WINDOWS ON RH

SIDE CONT OF AMIS ITEM 3782214 PROG TEXT: - ITEM ROLLED

FORWARD.

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP OR DOWN FOR MORE INFO PAGE 5 OF 7 »RU »RD

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/SMC004/ /*** / SERVICE OIL NBR 1 ENG. CHECK OIL QTY ON NBR

2 VIA EICAS AND SVC AS REQUIRED. INF: **EICAS OIL MINIMUM

18QTS** REF: MOP 04-002-01 MRM: 97901

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-UP OR DOWN FOR MORE INFO PAGE 6 OF 7 »RU »RD

»OLRDIS/ - / 6452/ F / - / ..../ OLR DISPLAY

STA: GSO IN: 9915-17FEB09-1-1624= OUT: - -

CHK: SMC DISP: NO PRI-1'S: 5 GATE: ZONE:

OTS: YES OILSVC DONE: NO

DO DID P NO MISSION

/SMC005/ /*** / LAVATORY WASTE LEVEL SERVICE CHECK INF:

ENSURE THAT THE FWD AND AFT WASTE TANK LEVELS ARE LESS THAN ONE

QUARTER FULL PRIOR TO DISPATCH PER LOCAL STATION PROCEDURES AND

RAMP GENERAL MANUAL 45-2-10 MRM: 97767

/DF: /CF: /PC: ...../SDR: ./MIR: ....- ..

/DD: /OPB: /METERS: /

ROLL-DOWN FOR MORE INFO PAGE 7 OF 7 »RD



, , ,

11 Responses to United Airlines Boeing 767 trashed by firefighting system

  1. allan pochop February 28, 2009 at 3:52 pm #

    WOW, always want to take the cheapest bid. Of course this company that installed this fire EX. system is bonded? Right?? Nope?? Don’t Know?
    What’s the Bu. Nu. on this A/C. With flight deck instrumentation requiring, extensive replacement. One may wish to avoid riding on it.

  2. anonymous March 2, 2009 at 4:22 pm #

    I can’t imagine why a mechanic would stand by and smile as a window shade shatters in someone’s face and an aircraft that is due to service the customers paying his check is damaged. Eastern Airlines had folks with the same though processes.

  3. Fernando Craff March 3, 2009 at 3:43 pm #

    UAL board of directors deserve to be in jail for being so corrupt. Always cutting expenses in the wrong places like their employees that worked so hard to build a good company. At the end, the ESOP was a complete failure leaving us without a penny, while these assholes got big bonnuses and pay raises. Too bad the government is sleeping with these kind od parasites. We should all raise and sue the company for lost ESOP shares.

  4. none March 3, 2009 at 8:05 pm #

    I only wish it would have happene to US Air.. They are just as deserving. LOL…

  5. Joannah March 18, 2009 at 5:38 am #

    I recently came across your blog and have been reading along. I thought I would leave my first comment. I don’t know what to say except that I have enjoyed reading. Nice blog. I will keep visiting this blog very often.

    Joannah

    http://2gbmemory.net

  6. Kieran Daly March 25, 2009 at 9:22 am #

    Thanks Joannah, glad you like it. I’ll try to keep posting as often as you keep looking!

  7. Brian September 13, 2009 at 5:20 am #

    This company is falling apart. I started there in June, 2000. I left in April 2005 to work for the railroads. At least RRB is a damn good retirement!

  8. Ahmad Dan-Hamidu December 30, 2009 at 10:32 am #

    Cutting corners…which cut back at the corner-cutter (the company in question).

  9. Ginger August 20, 2013 at 8:11 pm #

    New laws goals to reform the Patriot and FISA Amendments
    Acts to apply better oversight and management to the federal government’s surveillance packages. Fb did not roll out a Google Reader alternative at its press occasion last Thursday, however the firm may still be hard at work on a newsreading app. good facebook marketing (Ginger)

  10. how to win the lottery September 19, 2013 at 1:16 am #

    It’s wonderful that you are getting ideas from this article as well as from our argument made at this time.

  11. holosync September 24, 2013 at 8:09 pm #

    Your method of describing all in this post is truly pleasant, every one be able to without difficulty know it, Thanks a lot.

Leave a Reply